B5V1 Determination of individual and zone hazard ratings
Part B5 Cross-connection control
(1) Compliance with Performance Requirement B5P1 for individual protection and zone protection is verified by compliance with B5V1.
(2) A hazard exists wherever it is possible for water or contaminants to enter a non-drinking water service or supply via any potential cross-connection between itself and another separate non-drinking water service on the same site.
(3) Each hazard must be—
assigned a Hazard Rating in accordance with (4); and
isolated from the drinking water service by an appropriate backflow prevention device which is selected and installed for the appropriate Hazard Rating in accordance with Section 4 of AS/NZS 3500.1.
(4) To determine the Hazard Rating—
an assessment of the property or proposed installation must be undertaken using Tables B5V1a, B5V1b, B5V1c, B5V1d and B5V1e; and
the scores allocated from each table are calculated; and
the Hazard Rating is determined by the sum of the scores in accordance with B5V1(5).
(5) A total score of—
0 to 3 presents no Hazard; and
4 to 7 presents a Low Hazard; and
8 to 10 presents a Medium Hazard; and
11 or greater presents a High Hazard.
(6) Notwithstanding the Hazard Rating determined in (4), where access to the site is restricted in a way that could limit or prevent future testing or maintenance of a backflow prevention device, the site must be protected with a containment device suitable for a High Hazard.
Table B5V1a Building class
Site condition
Common examples
Notes
Score
The property to which the water service is installed contains a Class 1, 2, 7a, or 10 building where not more than 12 people reside.
Domestic residences and carparks with no associated activities.
Building may use small amounts of cleaning products, etc.
1
The property to which the water service is installed contains a Class 3, 4, 5, 6 or 7b building where chemical products are not stored.
Hostel, hotel and multi-level office.
Building is likely to have greater than 12 residents and/or occupants, and may contain moderate amounts of cleaning or commercial chemicals.
2
The property to which the water service is installed contains a Class 7b, 8 or 9 building where chemical products are stored.
Mechanical workshop, metal finisher, cleaning product wholesaler.
May contain large amounts of hazardous or toxic commercial chemicals.
3
Table B5V1b On-site water services
Site condition
Common examples
Notes
Score
There is only a drinking water supply and no other water sources to the property.
The drinking water source may be a rainwater tank connected to a detached dwelling.
Residential rainwater tanks are considered drinking water.
0
There is one drinking water supply and potentially other non-drinking water supplies or a separate fire-fighting water service available to the property (not applicable if the non-drinking water supply is Network Utility Operator provided recycled water with a sewerage source).
Network Utility Operatordrinking water supply and a separate fire water service.
Network Utility Operator supplied recycled water with a sewerage source is assessed separately due to greater health risks.
3
Commercial agriculture, farming, turf irrigation, industrial, processing or chemical industries. The property is supplied with drinking water and non-drinking water from multiple sources with potential for health related contamination.
Property has a Network Utility Operator drinking water source and an on-site wastewater effluent irrigation system, process water or bore water source.
Increased potential for cross-connection between drinking water and non-drinking water with high consequences such as chemicals, recycled sewerage, medical or biological contaminants.
5
Table B5V1c Drinking water use
Site condition
Common examples
Notes
Score
Drinking water use will not involve commercial use of hazardous or toxic substances and the site is unsuitable for their use and unlikely to change.
Domestic residences, offices and restaurants.
Minor use of cleaning and other chemicals is permitted. Professional or commercial hazardous chemical use is not permitted.
1
Drinking water will be used with commercial use hazardous substances, but not Schedule 1 to 4 or Schedule 6 to 8 poisons. Drinking water may be used with commercial use hazardous substances without major modification.
Butchers, hairdressers.
Hazardous substances and scheduled poisons have applicable warning labels. Cleaning of floors and benches with chlorine solution puts butchers into this category.
2
Drinking water use may involve large scale food or beverage processing, human or animal biological or faecal matter, Schedule 1 to 4 and Schedule 6 to 8 poisons and have potential for contamination. The installation is suitable for these uses without major modification. Also included are areas likely to undergo frequent changes of use or where the future use in unknown.
Chemical packaging facilities, hospital facilities, pan washing apparatus, fertiliser injection systems, chemical dispensers (high toxicity), food preparation fixtures with clean in place systems, industrial shed complexes and light commercial properties.
Wash down of spills puts chemicals packaging / storage into this category even if liquid batching and storage is not practised. Also applies where there is no certainty about the type of activities to be practiced and the materials used.
3
Table B5V1d Cross-connection type
Site condition
Common examples
Notes
Score
The product or installation presents no possibility of cross-connection to food, drink or water or other liquid vessels other than those used for domestic purposes.
Residential units and offices.
There are no water storage tanks, swimming pools, spas or commercial kitchens on site or able to be installed.
0
The product or installation presents a potential for a cross-connection between a drinking water service and a commercial food, drink or water or other liquid vessel, or any vessel intended for low hazard chemicals.
Small scale food processing facilities.
Potential backflow from low volume of non-hazardous substances. Non-hazardous chemicals are any substances not required to display a hazardous substance label.
1
The product or installation presents a potential for a cross-connection between a drinking water service and a non-drinking water service.
Drinking water outlets within close proximity to an alternative water source such as a Network Utility Operator drinking water supply, bore or irrigation system.
Potential connection of a drinking water system and a system identified with a Low Hazard.
2
The product or installation presents a potential for cross-connection between the drinking water service and a swimming pool, water storage tank used for commercial purposes, large scale food and drink processing operations, a vessel, pipe or body of liquid containing a hazardous substance or Schedule 5 poison, recycled water service with biological matter or faecal contamination.
Building header tanks, commercial swimming pool make up water connections, soft drink manufacturers.
Potential connection of a drinking water system and a system containing an hazardous substance or low toxicity poison or large quantities of food or drink product. Hazardous chemicals are any substances required to display a hazardous substance label.
3
The product or installation presents the potential for cross-connection between the drinking water service and a bulk water service vessel containing a hazardous substance or Schedule 5 poison.
Chemical make-up water connected to a chemical batching process.
Any potential connection to a system containing large volumes of hazardous material or moderately poisonous material.
4
The product or installation has potential for a cross-connection to a sewerage source, a trade waste source, a vessel with human or animal biological or faecal matter, a vessel pipe or body of liquid containing any quantity of a Schedule 1 to 4 or Schedule 6 to 8 poison.
Recycled water irrigation system with drinking water back up supply.
Applies t
Tables
- Table B5V1a Building class
- Table B5V1b On-site water services
- Table B5V1c Drinking water use
- Table B5V1d Cross-connection type
- Table B5V1e Extent of contamination
Changed in NCC 2025. See NCC 2025 Volume Three B5V1, or show what changed.
(1) Compliance with Performance Requirement B5P1 for individual protection and … wherever it is possible for water or contaminants to enter a non-drinking water service or supply via any potential or actual cross-connection between itself and another any other separate non-drinking water service on the same site. (3) Each hazard must … and installed for the appropriate Hazard Rating in accordance with Section 4 of AS/NZS 3500.1. (4) To determine the Hazard Rating — an … backflow prevention device, the site must be protected with a containment contaminant device suitable for a High Hazard. Table B5V1a Building class … Operator provided recycled water with a sewerage source). Network Utility Operatordrinking Operator drinking water supply and a separate fire water service. Network Utility … water irrigation system with drinking water back up supply. Applies t to potential connections with a hi
Removed words are struck through; added words are highlighted. Comparison of the text only.