B6P3 Water efficiency
Part B6 Rainwater services · NCC 2019: BP6.2
A rainwater service must ensure the efficient use of water by—
limiting water usage from—
a cistern or flushing device for a urinal, to a flush volume of not more than 2.5 litres for each—
single urinal stall; or
600 mm length of a continuous urinal wall; and
a dual flush cistern or flushing valve that is connected to a water closet pan, to a flush volume of not more than—
6 and 3 litres; or
4.5 and 3 litres; and
other rainwater using fixtures and appliances, to an efficient level; or
other water saving measures which achieve equivalent or greater efficiency than (a).
Applications
The flush volumes of B6P3 may be within a tolerance of—
±0.5 litres for the full flush of a 6/3 litre cistern; or
+0.5 litres for the reduced flush of a 6/3 litre cistern; or
±0.2 litres for a 4.5/3 litre cistern.
Exemptions
The requirements of B6P3(a)(ii) do not apply to a vacuum drainage system.
Changed in NCC 2025. See NCC 2025 Volume Three B6P3, or show what changed.
A Where rainwater service must ensure the is used for flushing of toilets or urinals, efficient use of water rainwater must be achieved by — limiting water usage from incorporation of — a cistern or flushing device for a urinal, to … — 6 and 3 litres; or 4.5 and 3 litres; and other rainwater using fixtures and appliances, to an efficient level; or other water saving measures which achieve equivalent or greater … of B6P3(a)(ii) do not apply to a vacuum drainage system.
Removed words are struck through; added words are highlighted. Comparison of the text only.