Verification Method · NCC 2022 Volume Three

C1V2 System 1 - Common discharge design

Part C1 Sanitary plumbing systems

Open C1V2 on NCC Online ↗

(1) Compliance with C1P5 for pipe sizing is verified for each common discharge branch when—

pipework is in accordance with (2); and

ventilation is in accordance with (3).

(2) Each unvented common discharge pipe within the system must have—

a pipe length from trap weir to stack less than 4 m; and

no more than three 90º bends, excluding the first bend after the trap outlet; and

no vertical drops of greater than 45º inclination between the trap weir and the stack greater than 1 m; and

a gradient greater than 1.00%; and

a pipe size in accordance with Table C1V2.

(3) Each vented common discharge pipe within the system must have—

a pipe length from trap weir to the stack of less than 10 m; and

no vertical drops of greater than 45º inclination, between the trap weir and the stack greater than 3 m; and

a gradient greater than 0.50%; and

a pipe size in accordance with Table C1V2; and

a group vent sized in accordance with Table C1V2; and

each group vent either—

terminates to atmosphere or interconnects with another vent in accordance with AS/NZS 3500.2; or

terminates at an air admittance valve with a minimum airflow rate equal to the wastewater design flowrate.

Limitations

Water closets must only be connected to a DN 80 or DN 100 discharge pipe.

Table C1V2 Common discharge pipe capacity

Common discharge pipe size - Nominal diameter (DN)

Unvented capacity QTotal - Litres per second (l/s)

Vented capacity QTotal - Litres per second (l/s)

Group vent - Nominal diameter (DN)

40

0.50

N/A

N/A

50

0.80

0.75

40

65

1.00

1.50

40

80

2.00

3.00

50

100

2.50

3.75

65

Tables

Changed in NCC 2025. See NCC 2025 Volume Three C1V2, or show what changed.

(1) Compliance with C1P5 for pipe sizing is verified for each common discharge branch the plumbing design when — pipework is fully vented systems and fully vented modified systems are designed in accordance with (2); Section 8 of AS/NZS 3500.2: and ventilation is single stack systems and single stack modified systems are designed in accordance with (3). Section 9 of AS/NZS 3500.2: and consideration by the designer is given to expanding the exclusion zones referenced in AS/NZS 3500.2 (1 m exclusion zone at the base of the stack) for high rise buildings. (2) Each unvented common discharge pipe within For the system must have — a pipe length from trap weir purposes of (1), for each pipework section, the probable simultaneous wastewater flowrate determined through C1V1 may be converted to stack less than 4 m; and no more than three 90º bends, excluding the first bend after the trap outlet; and no vertical drops of greater than 45º inclination between the trap weir and the stack greater than 1 m; and a gradient greater than 1.00%; and a pipe size an equivalent AS/NZS 3500.2 Fixture Unit [formula] in accordance with Table C1V2. the following: [formula] (3) Each vented common discharge pipe within In the system must have — equation shown at (2): [formula] = the wastewater flowrate (L/s); and [formula] = the equivalent fixture units converted from a pipe length from trap weir flowrate (dimensionless) where the result is rounded up to the stack next integer. (4) For the purposes of less than 10 m; (1), all relevant sizing tables and no vertical drops design guidance referencing [formula] in AS/NZS 3500.2 may alternatively be converted to an equivalent flowrate using the following: [formula] (5) In the equation shown at (4), [formula] = the sum of greater than 45º inclination, between the trap weir and the stack greater than 3 m; and a gradient greater than 0.50%; and a pipe size in accordance with Table C1V2; and a group vent sized in accordance with Table C1V2; and each group vent either — terminates fixture units to atmosphere or interconnects with another vent in accordance with AS/NZS 3500.2; or terminates at an air admittance valve with a minimum airflow rate equal to the wastewater design flowrate. Limitations Water closets must only be connected to a DN 80 or DN 100 discharge pipe. Table C1V2 Common discharge pipe capacity Common discharge pipe size - Nominal diameter (DN) Unvented capacity QTotal - Litres per second (l/s) Vented capacity QTotal - Litres per second (l/s) Group vent - Nominal diameter (DN) 40 0.50 N/A N/A 50 0.80 0.75 40 65 1.00 1.50 40 80 2.00 3.00 50 100 2.50 3.75 65 converted (dimensionless).