C1P5 Ventilation
Part C1 Sanitary plumbing systems · NCC 2019: CP1.1
A sanitary plumbing system must ensure that ventilation is provided to avoid hydraulic load imbalance such that—
there is less than a 1% likelihood during the annual peak hour that when any fixture discharges, air pressure at any trap seal exceeds ±375 Pa difference from atmospheric pressure; or
an equivalent level of safety to human health is achieved as a system complying to (a).
Exemptions
C1P5 Ventilation does not apply to vacuum drainage systems.
Changed in NCC 2025 (minor wording). See NCC 2025 Volume Three C1P5, or show what changed.
A sanitary plumbing system must ensure that ventilation is provided … — there is less than a 1% likelihood during the annual peak hour that when any fixture discharges, air pressure at … Exemptions C1P5 Ventilation does not apply to vacuum drainage systems.