NCC 2022 Volume Three
Part C1 Sanitary plumbing systems
27 clauses · Open on NCC Online ↗
- C1O1 ObjectiveThe Objective of this Part is to— safeguard people from illness, injury or loss (including loss of amenity) due to the failure of a sanitary…
- C1F1 Disposal systemSanitary fixtures and sanitary appliances must be provided with an adequate disposal system that does not impact adversely on the occupants of the…
- C1P1 DisposalA sanitary plumbing system must ensure sewage or sullage is transferred to a sanitary drainage system or an approved disposal system.
- C1P2 AccessA sanitary plumbing system must ensure access for maintenance of mechanical components, operational controls and for clearing blockages.
- C1P3 Water efficiencyA sanitary plumbing system must ensure efficient use of drinking water by— limiting water usage from— a cistern or flushing device for a urinal, to…
- C1P4 Uncontrolled dischargeA sanitary plumbing system must avoid blockage or uncontrolled discharge.
- C1P5 VentilationA sanitary plumbing system must ensure that ventilation is provided to avoid hydraulic load imbalance such that— there is less than a 1% likelihood…
- C1P6 ContaminationA sanitary plumbing system must avoid— entry of water, sewerage and sullage from the system into buildings; and entry of foul gases from the system…
- C1P7 DamageA sanitary plumbing system must avoid damage from superimposed loads, ground movement or root penetration.
- Table C1V1a Frequency factorsFixture usage | NCC building classes | Frequency factor (K) Intermittent use e.g. dwelling, guesthouse or office | Class 1, Class 2, Class 3 or…
- Table C1V1b Discharge unitsFixture | System 1 | System 2 | System 3 Basin | 0.5 | 0.3 | 0.3 Shower | 0.6 | 0.4 | 0.4 Urinal | 0.8 | 0.5 | 0.4 Bath | 0.8 | 0.6 | 1.3 Kitchen…
- C1V1 Determination of sanitary plumbing wastewater flowratesCompliance with C1P3 for pipe sizing is verified for each sanitary plumbing pipework section when the discharge flowrate is not less than the…
- Table C1V2 Common discharge pipe capacityCommon discharge pipe size - Nominal diameter (DN) | Unvented capacity QTotal - Litres per second (l/s) | Vented capacity QTotal - Litres per second…
- C1V2 System 1 - Common discharge designCompliance with C1P5 for pipe sizing is verified for each common discharge branch when— pipework is in accordance with (2); and ventilation is in…
- Table C1V3 System 2 - Common discharge pipe capacityCommon discharge pipe - Nominal diameter (DN) | Unvented capacity QTotal - Litres per second (l/s) | Vented capacity QTotal - Litres per second…
- C1V3 System 2 - Common discharge designCompliance with C1P5 relating to pipe sizing is verified for each common discharge branch when— pipework is in accordance with (2); and ventilation…
- Table C1V4a System 3 - Unvented fixture connectionsFixture | Waste Nominal Diameter (DN) | Maximum length, in metres (m) | Minimum gradient (%) | Maximum gradient (%) | Maximum number of bends |…
- Table C1V4b System 3 - Vented fixture connectionsFixture | Waste Nominal Diameter (DN) | Maximum length, in metres (m) | Minimum gradient (%) | Maximum gradient (%) | Maximum number of bends |…
- C1V4 System 3 - Branch designCompliance with C1P5 relating to pipe sizing is verified for each discharge branch when— each unvented fixture, or combination of fixtures, connects…
- Table C1V5a Stack capacity without a relief ventStack Nominal Diameter (DN) | Capacity with square or 88° junction, in litres per second (l/s) | Capacity with sweep or 45° junction, in litres per…
- Table C1V5b Stack capacity with a relief ventStack Nominal Diameter (DN) | Capacity with square or 88° junction, in litres per second (l/s) | Capacity with sweep or 45° junction, in litres per…
- C1V5 Stack designCompliance with C1P5 relating to pipe sizing is verified for the stack system when— each stack has a pipe size in accordance with (2); and…
- C1D1 Deemed-to-Satisfy ProvisionsWhere a Deemed-to-Satisfy Solution is proposed, Performance Requirement C1P1 to C1P7 is satisfied by complying with C1D2 and C1D5. (2) Where a…
- C1D2 Invert levelsThe invert level of a trap or gully weir must be a minimum of 10 mm higher than the soffit of the pipe to which it connects.
- C1D3 General requirements SA VICA sanitary plumbing system must be in accordance with AS/NZS 3500.2.
- C1D4 Bushfire prone areasA sanitary plumbing system in a designated bushfire prone area must be in accordance with AS 3959.
- C1D5 Water efficiencyA sanitary plumbing system must ensure the efficient use of drinking water by— limiting water usage from— a cistern or flushing device for a urinal,…