Verification Method · NCC 2022 Volume Three

C1V3 System 2 - Common discharge design

Part C1 Sanitary plumbing systems

Open C1V3 on NCC Online ↗

(1) Compliance with C1P5 relating to pipe sizing is verified for each common discharge branch when—

pipework is in accordance with (2); and

ventilation is provided in accordance with (3).

(2) Each unvented common discharge pipe within the system must have—

a pipe length from trap weir to stack less than 10 m; and

no more than one 90º bend, excluding the first bend after the trap outlet; and

no vertical drops of greater than 45º inclination between the trap weir and the stack, greater than—

1 m, where a water closet is connected to the branch; or

3 m, where no water closets are connected to the branch; and

a gradient greater than 1.50%; and

a pipe size in accordance with Table C1V3.

(3) Each vented common discharge pipe within the system has—

no vertical drops of greater than 45º inclination between the trap weir and the stack greater than 3 m; and

a gradient greater than 1.50%; and

a pipe size in accordance with Table C1V3; and

a group vent sized in accordance with Table C1V3; and

each group vent either—

terminates to atmosphere or interconnects with another vent in accordance with AS/NZS 3500.2; or

terminates to an air admittance valve with a minimum airflow rate equal to 2 times the wastewater design flowrate.

Limitations

Water closets must only be connected to a DN 80 or DN 100 discharge pipe.

No more than one water closet can be connected to a DN 80 discharge pipe.

Table C1V3 System 2 - Common discharge pipe capacity

Common discharge pipe - Nominal diameter (DN)

Unvented capacity QTotal - Litres per second (l/s)

Vented capacity QTotal - Litres per second (l/s)

Group vent - Nominal diameter (DN)

40

0.50

0.75

32

50

1.00

1.50

32

65

1.50

2.25

40

80

2.25

3.40

40

100

2.50

3.75

50

Tables

Not in NCC 2025. No C1V3 in NCC 2025 Volume Three.