Specification clause · NCC 2022 Volume Three

S41C3 Protection types and hazard ratings

Specification 41 Cross-connection hazards · NCC 2019: BS5.1.3

Open S41C3 on NCC Online ↗
Varied in VIC. Check the variation for your state.

(1) Cross-connection hazards within the site must be rated in accordance with—

S41C4 for individual protection at the point of each individual hazard; or

S41C5 for zone protection at the point where a group of hazards can be isolated.

(2) The hazard posed by the site to the Network Utility Operator’s drinking water supply must be rated for containment protection in accordance with S41C6.

(3) Pipework and outlets supplied by a drinking water source downstream of an individual protection backflow prevention device are considered to convey drinking water from an unprotected water service.

Not in NCC 2025. No S41C3 in NCC 2025 Volume Three.