Tasmania variation · NCC 2022 Volume Three

TAS B1P5 Pressure

Part B1 Cold water services · varies B1P5 Pressure

Open on NCC Online ↗

Delete clause B1P5 and insert TAS B1P5 as follows:

The points of discharge for a cold water service must—

have—

a working pressure of not less than 50 kPa; and

a static pressure within the building of not more than 500 kPa; or

have water pressures suitable for the correct functioning of the fixture or appliance where water pressures outside of (a)(i) and (a)(ii) are required.

Exemptions

B1P5(a)(i) and B1P5(a)(ii) do not apply to existing low-pressure gravity only water services.

Not in NCC 2025. No TAS B1P5 in NCC 2025 Volume Three.