B1P5 Pressure
Part B1 Cold water services · NCC 2019: BP1.2, TAS Exemption 1
The points of discharge for a cold water service must—
have—
a working pressure of not less than 50 kPa; and
a static pressure within the building of not more than 500 kPa; or
have water pressures suitable for the correct functioning of the fixture or appliance where water pressures outside of (a)(i) and (a)(ii) are required.
Changed in NCC 2025. See NCC 2025 Volume Three B1P5, or show what changed.
The points of discharge for Where a cold water service is used, efficient use of drinking water must be achieved by — have incorporation of — a working pressure of not less than 50 kPa; and tap or outlet for a static pressure within the building shower, basin, kitchen sink or laundry trough, to a flow rate of not more than 500 kPa; 9 l/m; and a cistern or have flushing device for a urinal, to a flush volume of not more than 2.5 litres for each — single urinal stall; or 600 mm length of a continuous urinal wall; and a dual flush cistern or flushing valve that is connected to a water pressures suitable closet pan to a flush volume of not more than — 6 and 3 litres; or 4.5 and 3 litres; or water saving measures equivalent to or greater than those described in (a). Applications The flush volumes of B1P5 may be within a tolerance of — ±0.5 litres for the correct functioning full flush of a 6/3 litre cistern; or +0.5 litres for the fixture reduced flush of a 6/3 litre cistern; or appliance where water pressures outside ±0.2 litres for a 4.5/3 litre cistern. Exemptions The requirements of (a)(i) and (a)(ii) are required. B1P5 do not apply to a vacuum drainage system.