Deemed-to-Satisfy Provision · NCC 2022 Volume Two

H1D5 Masonry

Part H1 Structure · NCC 2019: 3.3.1-3.3.3, 3.3.5-3.3.6

Open H1D5 on NCC Online ↗

(1) Performance RequirementH1P1 is satisfied for masonry veneer if it is designed and constructed in accordance with—

AS 3700; or

AS 4773.1 and AS 4773.2; or

Part 5.2 of the ABCB Housing Provisions provided—

the building is located in an area with a wind class of not more than N3; and

masonry veneer walls—

are constructed on footings and/or slabs that comply with H1D4; and

comply with Part 5.6 using components that comply with Part 5.7 of the ABCB Housing Provisions; and

the building site soil classification is A, S or M in accordance with AS 2870; and

the framing that the masonry wall is tied to complies with H1D6; and

the building is not constructed in an alpine area; and

the building is one for which Appendix A of AS 1170.4 contains no specific earthquake design requirements.

(2) Performance RequirementH1P1 is satisfied for cavity brick unreinforced masonry if it is designed and constructed in accordance with:

AS 3700; or

AS 4773.1 and AS 4773.2; or

Part 5.3 of the ABCB Housing Provisions provided—

the building is located in an area with a design wind speed of not more than N3; and

cavity masonry walls—

are constructed on footings and/or slabs that comply with H1D4; and

comply with Part 5.6 using components that comply with Part 5.7 of the ABCB Housing Provisions; and

the building site soil classification is A, S or M in accordance with AS 2870; and

the building is not constructed in an alpine area; and

the building is one for which Appendix A of AS 1170.4 contains no specific earthquake design requirements.

(3) Performance RequirementH1P1 is satisfied for single leaf unreinforced masonry if it is designed and constructed in accordance with:

AS 3700; or

AS 4773.1 and AS 4773.2; or

Part 5.4 of the ABCB Housing Provisions provided—

the building is located in an area with a design wind speed of not more than N3; and

single leaf unreinforced masonry walls—

are constructed on footings and/or slabs that comply with H1D4; and

comply with Part 5.6 using components that comply with Part 5.7 of the ABCB Housing Provisions; and

the building site soil classification is A, S or M in accordance with AS 2870; and

the building is not constructed in an alpine area; and

the building is one for which Appendix A of AS 1170.4 contains no specific earthquake design requirements.

(4) Performance RequirementH1P1 is satisfied for reinforced masonry if it is designed and constructed in accordance with:

AS 3700, except—

‘(for piers—isolated or engaged)’ is removed from clause 8.5.1(d); and

where clause 8.5.1 requires design as for unreinforced masonry in accordance with Section 7, the member must also be designed as unreinforced masonry in accordance with Table 10.3 and 4.1(a)(i)(C) of AS 3700; or

AS 4773.1 and AS 4773.2.

(5) Performance RequirementH1P1 is satisfied for an isolated masonry pier system if it is designed and constructed in accordance with one of the following, as appropriate:

AS 3700, except—

‘(for piers—isolated or engaged)’ is removed from clause 8.5.1(d); and

where clause 8.5.1 requires design as for unreinforced masonry in accordance with Section 7, the member must also be designed as unreinforced masonry in accordance with Table 10.3 and 4.1(a)(i)(C) of AS 3700.

AS 4773.1 and AS 4773.2.

Part 5.5 of the ABCB Housing Provisions provided—

the building is located in an area with a wind class of not more than N3; and

isolated piers are constructed on footings and/or slabs that comply with H1D4; and

masonry units comply with 5.6.2(4) of the ABCB Housing Provisions and have a minimum compressive strength of—

6.2 MPa for solid or cored units; or

15 MPa for hollow units; and

the roof structure and any walls provide the required lateral bracing for the top of the isolated pier when determined in accordance with AS 3700, except—

‘(for piers—isolated or engaged)’ is removed from clause 8.5.1(d); and

where clause 8.5.1 requires design as for unreinforced masonry in accordance with Section 7, the member must also be designed as unreinforced masonry in accordance with Table 10.3 and 4.1(a)(i)(C) of AS 3700; and

the building site soil classification is A, S or M in accordance with AS 2870; and

the building is not constructed in an alpine area; and

the building is one for which Appendix A of AS 1170.4 contains no specific earthquake design requirements.

(6) Performance RequirementH1P1 is satisfied for masonry accessories if they are constructed and installed in accordance with:

AS 3700; or

AS 4773.1 and AS 4773.2.

Part 5.6 of the ABCB Housing Provisions provided—

the building is located in an area with a wind class of not more than N3; and

the building is not constructed in an alpine area; and

the building is one for which Appendix A of AS 1170.4 contains no specific earthquake design requirements.

Same wording in NCC 2025 Volume Two. See NCC 2025 Volume Two H1D5.