H1D5 Masonry
Part H1 Structure · NCC 2019: 3.3.1-3.3.3, 3.3.5-3.3.6
(1) Performance Requirement H1P1 is satisfied for masonry veneer if it is designed and constructed in accordance with—
AS 3700; or
AS 4773.1 and AS 4773.2; or
Part 5.2 of the ABCB Housing Provisions provided—
the building is located in an area with a wind class of not more than N3; and
masonry veneer walls—
are constructed on footings and/or slabs that comply with H1D4; and
comply with Part 5.6 using components that comply with Part 5.7 of the ABCB Housing Provisions; and
the building site soil classification is A, S or M in accordance with AS 2870; and
the framing that the masonry wall is tied to complies with H1D6; and
the building is not constructed in an alpine area; and
the building is one for which Appendix A of AS 1170.4 contains no specific earthquake design requirements.
(2) Performance Requirement H1P1 is satisfied for cavity brick unreinforced masonry if it is designed and constructed in accordance with:
AS 3700; or
AS 4773.1 and AS 4773.2; or
Part 5.3 of the ABCB Housing Provisions provided—
the building is located in an area with a design wind speed of not more than N3; and
cavity masonry walls—
are constructed on footings and/or slabs that comply with H1D4; and
comply with Part 5.6 using components that comply with Part 5.7 of the ABCB Housing Provisions; and
the building site soil classification is A, S or M in accordance with AS 2870; and
the building is not constructed in an alpine area; and
the building is one for which Appendix A of AS 1170.4 contains no specific earthquake design requirements.
(3) Performance Requirement H1P1 is satisfied for single leaf unreinforced masonry if it is designed and constructed in accordance with:
AS 3700; or
AS 4773.1 and AS 4773.2; or
Part 5.4 of the ABCB Housing Provisions provided—
the building is located in an area with a design wind speed of not more than N3; and
single leaf unreinforced masonry walls—
are constructed on footings and/or slabs that comply with H1D4; and
comply with Part 5.6 using components that comply with Part 5.7 of the ABCB Housing Provisions; and
the building site soil classification is A, S or M in accordance with AS 2870; and
the building is not constructed in an alpine area; and
the building is one for which Appendix A of AS 1170.4 contains no specific earthquake design requirements.
(4) Performance Requirement H1P1 is satisfied for reinforced masonry if it is designed and constructed in accordance with:
AS 3700, except—
‘(for piers—isolated or engaged)’ is removed from clause 8.5.1(d); and
where clause 8.5.1 requires design as for unreinforced masonry in accordance with Section 7, the member must also be designed as unreinforced masonry in accordance with Table 10.3 and 4.1(a)(i)(C) of AS 3700; or
AS 4773.1 and AS 4773.2.
(5) Performance Requirement H1P1 is satisfied for an isolated masonry pier system if it is designed and constructed in accordance with one of the following, as appropriate:
AS 3700, except—
‘(for piers—isolated or engaged)’ is removed from clause 8.5.1(d); and
where clause 8.5.1 requires design as for unreinforced masonry in accordance with Section 7, the member must also be designed as unreinforced masonry in accordance with Table 10.3 and 4.1(a)(i)(C) of AS 3700.
AS 4773.1 and AS 4773.2.
Part 5.5 of the ABCB Housing Provisions provided—
the building is located in an area with a wind class of not more than N3; and
isolated piers are constructed on footings and/or slabs that comply with H1D4; and
masonry units comply with 5.6.2(4) of the ABCB Housing Provisions and have a minimum compressive strength of—
6.2 MPa for solid or cored units; or
15 MPa for hollow units; and
the roof structure and any walls provide the required lateral bracing for the top of the isolated pier when determined in accordance with AS 3700, except—
‘(for piers—isolated or engaged)’ is removed from clause 8.5.1(d); and
where clause 8.5.1 requires design as for unreinforced masonry in accordance with Section 7, the member must also be designed as unreinforced masonry in accordance with Table 10.3 and 4.1(a)(i)(C) of AS 3700; and
the building site soil classification is A, S or M in accordance with AS 2870; and
the building is not constructed in an alpine area; and
the building is one for which Appendix A of AS 1170.4 contains no specific earthquake design requirements.
(6) Performance Requirement H1P1 is satisfied for masonry accessories if they are constructed and installed in accordance with:
AS 3700; or
AS 4773.1 and AS 4773.2.
Part 5.6 of the ABCB Housing Provisions provided—
the building is located in an area with a wind class of not more than N3; and
the building is not constructed in an alpine area; and
the building is one for which Appendix A of AS 1170.4 contains no specific earthquake design requirements.