Verification Method · NCC 2022 Volume Two

H3V4 Avoidance of spread of fire between Class 2-9 buildings

Part H3 Fire safety · NCC 2019: V2.3.1.4

Open H3V4 on NCC Online ↗

Compliance with H3P1(2) to avoid a Class 10a building increasing the risk of fire spread between Class 2-9 buildings is verified when it is calculated that a building—

is capable of withstanding the heat flux set out in column 2 of Table H3V4 without ignition; and

will not cause heat flux in excess of those set out in column 2 of Table H3V4, when the distance between the buildings is as set out in column 1 of Table H3V4.

Table H3V4 Heat flux (same allotment)

Column 1 (Location)

Column 2 (Heat flux [kW/m2])

0 m

80

2 m

40

6 m

20

12 m

10

Tables

Same wording in NCC 2025 Volume Two. See NCC 2025 Volume Two H3V4.