Verification Method · NCC 2025 Volume Two
H3V4 Avoidance of spread of fire between Class 2-9 buildings
Part H3 Fire safety · NCC 2019: V2.3.1.4
Compliance with H3P1(2) to avoid a Class 10a building increasing the risk of fire spread between Class 2-9 buildings is verified when it is calculated that a building—
is capable of withstanding the heat flux set out in column 2 of Table H3V4 without ignition; and
will not cause heat flux in excess of those set out in column 2 of Table H3V4, when the distance between the buildings is as set out in column 1 of Table H3V4.
Table H3V4 Heat flux (same allotment)
Column 1 (Location)
Column 2 (Heat flux [kW/m2])
0 m
80
2 m
40
6 m
20
12 m
10
Tables
Same wording in NCC 2022 Volume Two. See NCC 2022 Volume Two H3V4.