Verification Method · NCC 2022 Volume Two

H4V3 Verification of indoor air quality

Part H4 Health and amenity · NCC 2019: V2.4.5

Open H4V3 on NCC Online ↗

For a Class 1 building, compliance with H4P5(1) and H4P5(2)(a) is verified when it is determined that the building under typical conditions in use is provided with sufficient ventilation with outdoor air such that contaminant levels do not exceed the limits specified in Table H4V3.

Table H4V3 Maximum contaminant limits for acceptable indoor air quality

Pollutant

Averaging Time

Maximum Air Quality Value

Carbon dioxide, CO2

8 hours

850 ppm Note 1

Carbon monoxide, CO

15 minutes

90 ppm

Carbon monoxide, CO

30 minutes

50 ppm

Carbon monoxide, CO

1 hour

25 ppm

Carbon monoxide, CO

8 hours

10 ppm

Formaldehyde, CH2O

30 minutes

0.1 mg/m3

Nitrogen dioxide, NO2

1 year

40 μg/m3 (0.0197 ppm) Note 2

Nitrogen dioxide, NO2

1 hour

200 μg/m3 (0.0987 ppm) Note 2

Ozone, O3

8 hour, daily maximum

100 μg/m3 (0.0473 ppm)

Particulate matter, PM2.5

1 year

10 μg/m3

Particulate matter, PM2.5

24 hour (99th percentile)

25 μg/m3

Particulate matter, PM10

1 year

20 μg/m3

Particulate matter, PM10

24 hour (99th percentile)

50 μg/m3

Total volatile organic compounds

1 hour

500 μg/m3

Table Notes

Based on body odour metric (i.e. 450 ppm above ambient CO2 level of 400 ppm and demand control ventilation provisions in AS 1668.2).

Based on pressure of 101.325 kPa and temperature of 25 degrees (i.e. the conversion is mg/m3 = ppm (molecular weight/24.4)).

Tables

Same wording in NCC 2025 Volume Two. See NCC 2025 Volume Two H4V3.

Clauses referred to

Defined terms used