H4V3 Verification of indoor air quality
Part H4 Health and amenity · NCC 2019: V2.4.5
For a Class 1 building, compliance with H4P5(1) and H4P5(2)(a) is verified when it is determined that the building under typical conditions in use is provided with sufficient ventilation with outdoor air such that contaminant levels do not exceed the limits specified in Table H4V3.
Table H4V3 Maximum contaminant limits for acceptable indoor air quality
Pollutant
Averaging Time
Maximum Air Quality Value
Carbon dioxide, CO2
8 hours
850 ppm Note 1
Carbon monoxide, CO
15 minutes
90 ppm
Carbon monoxide, CO
30 minutes
50 ppm
Carbon monoxide, CO
1 hour
25 ppm
Carbon monoxide, CO
8 hours
10 ppm
Formaldehyde, CH2O
30 minutes
0.1 mg/m3
Nitrogen dioxide, NO2
1 year
40 μg/m3 (0.0197 ppm) Note 2
Nitrogen dioxide, NO2
1 hour
200 μg/m3 (0.0987 ppm) Note 2
Ozone, O3
8 hour, daily maximum
100 μg/m3 (0.0473 ppm)
Particulate matter, PM2.5
1 year
10 μg/m3
Particulate matter, PM2.5
24 hour (99th percentile)
25 μg/m3
Particulate matter, PM10
1 year
20 μg/m3
Particulate matter, PM10
24 hour (99th percentile)
50 μg/m3
Total volatile organic compounds
1 hour
500 μg/m3
Table Notes
Based on body odour metric (i.e. 450 ppm above ambient CO2 level of 400 ppm and demand control ventilation provisions in AS 1668.2).
Based on pressure of 101.325 kPa and temperature of 25 degrees (i.e. the conversion is mg/m3 = ppm (molecular weight/24.4)).