Verification Method · NCC 2022 Volume Two

H4V5 Verification of condensation management

Part H4 Health and amenity · NCC 2019: V2.4.7

Open H4V5 on NCC Online ↗

(1) Compliance with Performance Requirement H4P7 is verified for a roof or external wall assembly when it is determined that a mould index of greater than 3, as defined by Section 6 of AIRAH DA07, does not occur on—

the interior surface of the water control layer; or

the surfaces of building fabric components interior to the water control layer.

(2) The calculation method for (1) must use—

input assumptions in accordance with AIRAH DA07; and

the intermediate method for calculating indoor design humidity in Section 4.3.2 of AIRAH DA07.

Same wording in NCC 2025 Volume Two. See NCC 2025 Volume Two H4V5.

Clauses referred to

Defined terms used