Verification Method · NCC 2025 Volume Two
H4V5 Verification of condensation management
Part H4 Health and amenity · NCC 2019: V2.4.7
(1) Compliance with Performance Requirement H4P7 is verified for a roof or external wall assembly when it is determined that a mould index of greater than 3, as defined by Section 6 of AIRAH DA07, does not occur on—
the interior surface of the water control layer; or
the surfaces of building fabric components interior to the water control layer.
(2) The calculation method for (1) must use—
input assumptions in accordance with AIRAH DA07; and
the intermediate method for calculating indoor design humidity in Section 4.3.2 of AIRAH DA07.
Same wording in NCC 2022 Volume Two. See NCC 2022 Volume Two H4V5.