Deemed-to-Satisfy Provision · NCC 2022 Volume Two

H7D2 Swimming pools

Part H7 Ancillary provisions and additional construction requirements · NCC 2019: NSW 3.10.1.0, 3.10.1

Open H7D2 on NCC Online ↗
Varied in NSW, NT, QLD, SA, TAS. Check the variation for your state.

(1) Performance RequirementH7P1 is satisfied for a swimming pool with a depth of water more than 300 mm and which is associated with a Class 1 building, if it has safety barriers installed in accordance with AS 1926.1 and AS 1926.2.

(2) Performance RequirementH7P2 is satisfied for a water recirculation system of a swimming pool with a depth of water more than 300 mm, if it complies with AS 1926.3.

Changed in NCC 2025. See NCC 2025 Volume Two H7D2, or show what changed.

(1) Performance RequirementH7P1 Requirement H7P1 is satisfied for a swimming pool with a depth of … building, if it has safety barriers installed in accordance with — AS 1926.1 1926.1, except ‘This clause shall not apply to boundary barriers.’ in clause 2.3.1 is replaced with ‘This clause shall apply to boundary barriers.’; and AS 1926.2. (2) Performance RequirementH7P2 Requirement H7P2 is satisfied for a water recirculation system of a swimming … more than 300 mm, if it complies with AS 1926.3.

Removed words are struck through; added words are highlighted. Comparison of the text only.

State and territory variations all clauses side by side →

Defined terms used