Table S1C2h FRLs deemed to be achieved by hot-rolled steel columns (including a fabricated column) exposed on no more than 4 sides
Specification 1 Fire-resistance of building elements
| Fire protection | Minimum thickness (mm) of principal material for FRLs | ||||
|---|---|---|---|---|---|
| 60/–/– | 90/–/– | 120/–/– | 180/–/– | 240/–/– | |
| Concrete cast in-situ — load bearing | 25 | 40 | 45 | 65 | 90 |
| Concrete cast in-situ — non-load bearing unplastered | 25 | 30 | 40 | 50 | 65 |
| Concrete cast in-situ — non-load bearing plastered 13 mm | 25 | 25 | 30 | 40 | 50 |
| Gypsum cast in-situ | - | - | - | - | 50 |
| Gypsum — perlite or gypsum-vermiculite plaster — sprayed to contour | 25 | 30 | 40 | 55 | 65 |
| Gypsum — perlite or gypsum-vermiculite plaster — sprayed on metal lath | 20 | 20 | 30 | 40 | 50 |
Table Notes
For the purposes of this table, each element must meet the requirements of Specification 2.
Table for S1C2 Rating
Changed since NCC 2022. See NCC 2022 Volume Two Table S1C2h, or show what changed.
Fire protection | Minimum thickness (mm) of principal material for FRLs 60/–/– | 90/–/– | 120/–/– | 180/–/– | 240/–/– Concrete cast in-situ — loadbearing load bearing | 25 | 40 | 45 | 65 | 90 Concrete cast in-situ — non-loadbearing non-load bearing unplastered | 35 25 | 30 | 40 | 50 | 65 Concrete cast in-situ — non-loadbearing non-load bearing plastered 13 mm | 25 | 25 | 30 | … table, each element must meet the requirements of Specification 2.
Removed words are struck through; added words are highlighted. Comparison of the text only.