13.6.2 Net equivalent energy usage
Part 13.6 Whole-of-home energy usage
(1) The net equivalent energy usage of a building, calculated in accordance with (a), must not exceed the allowance calculated in accordance with (b)—
[formula] , where—
[formula] = the floor area factor obtained by multiplying the total floor area of the building by the adjustment factor in Table 13.6.2a; and
[formula] = the main space conditioning and main water heater efficiency factor obtained from the ABCB Standard for Whole-of-Home Efficiency Factors; and
[formula] = the swimming pool pump energy usage in (2); and
[formula] = the spa pump energy usage in (3); and
[formula] = the installed capacity of on-site photovoltaics (kW); and
[formula] , where—
[formula] = the floor area factor obtained from multiplying the total floor area of the building by the adjustment factor in Table 13.6.2a; and
[formula] = the energy factor obtained from in Table 13.6.2b.
(2)
The swimming pool pump energy usage (EP) must be determined in accordance with the following formula: [formula] , where—
[formula] = the swimming pool pump energy usage; and
[formula] = the volume of the swimming pool to the nearest 1000 litres; and
[formula] = the swimming pool pump factor as per Table 13.6.2c.
(3)
The spa pump energy usage (ES) must be determined in accordance with the following formula: [formula] , where—
[formula] = the spa pump energy usage; and
[formula] = the volume of the spa to the nearest 100 litres; and
[formula] = the spa pump factor as per Table 13.6.2d.
Table 13.6.2a Floor area adjustment factor
Total floor area m2
Floor area factor
Total floor area m2
Floor area factor
Total floor area m2
Floor area factor
Total floor area m2
Floor area factor
<50
0.0123
160–169
0.0097
280–289
0.0087
400–409
0.0080
50–59
0.0119
170–179
0.0096
290–299
0.0086
410–419
0.0079
60–69
0.0116
180–189
0.0095
300–309
0.0085
420–429
0.0079
70–79
0.0113
190–199
0.0094
310–319
0.0085
430–439
0.0078
80–89
0.0111
200–209
0.0093
320–329
0.0084
440–449
0.0078
90–99
0.0108
210–219
0.0092
330–339
0.0083
450–459
0.0077
100–109
0.0106
220–229
0.0091
340–349
0.0083
460–469
0.0077
110–119
0.0105
230–239
0.0090
350–359
0.0082
470–479
0.0077
120–129
0.0103
240–249
0.0090
360–369
0.0082
480–489
0.0076
130–139
0.0101
250–259
0.0089
370–379
0.0081
490–499
0.0076
140–149
0.0100
260–269
0.0088
380–389
0.0081
500
0.0075
150–159
0.0099
270–279
0.0087
390–399
0.0080
—
—
Table Notes
The total floor area is measured within the inside face of the external walls of the Class 1 building and includes any conditioned, attached Class 10a building.
Where values fall between ranges given, the floor area must be rounded up to the nearest whole square metres of floor area.
Table 13.6.2b Energy factor (EF)
Climate zone
ACT
NSW
NT
Qld
SA
Tas
Vic
WA
1
—
—
1.91
2.77
—
—
—
3.25
2
—
1.32
—
1.78
—
—
—
—
3
—
—
1.23
2.46
—
—
—
2.87
4
—
1.80
—
—
1.86
—
1.25
2.34
5
—
1.75
—
2.28
1.79
—
—
2.35
6
—
2.40
—
—
2.51
—
1.63
3.20
7
2.56
2.33
—
—
—
3.08
1.62
—
8
—
3.99
—
—
—
3.92
2.82
—
Table 13.6.2c Swimming pool pump factor (FP) (kW/1000 litres.annum)
Pool pump GEMS star rating
ACT
NSW
NT
Qld
SA
Tas
Vic
WA
1 or unrated
0.056
0.060
0.028
0.046
0.068
0.061
0.049
0.063
1.5
0.048
0.050
0.023
0.039
0.057
0.052
0.041
0.053
2
0.041
0.044
0.020
0.034
0.050
0.045
0.036
0.046
2.5
0.037
0.039
0.018
0.030
0.044
0.040
0.032
0.041
3
0.033
0.035
0.016
0.027
0.039
0.035
0.028
0.036
3.5
0.029
0.031
0.014
0.024
0.035
0.032
0.025
0.033
4
0.026
0.028
0.013
0.021
0.032
0.029
0.023
0.029
4.5
0.024
0.025
0.012
0.019
0.029
0.026
0.021
0.027
5
0.022
0.023
0.011
0.018
0.026
0.023
0.019
0.024
5.5
0.020
0.021
0.010
0.016
0.023
0.021
0.017
0.022
6
0.018
0.019
0.009
0.014
0.021
0.019
0.015
0.020
6.5
0.016
0.017
0.008
0.013
0.019
0.017
0.014
0.018
7
0.014
0.015
0.007
0.012
0.017
0.016
0.012
0.016
7.5
0.013
0.013
0.006
0.010
0.015
0.014
0.011
0.014
8
0.011
0.012
0.006
0.009
0.014
0.012
0.010
0.013
8.5
0.010
0.011
0.005
0.008
0.012
0.011
0.009
0.011
9
0.009
0.009
0.004
0.007
0.011
0.010
0.008
0.010
9.5
0.008
0.008
0.004
0.006
0.009
0.008
0.007
0.009
10
0.007
0.007
0.003
0.005
0.008
0.007
0.006
0.007
Table 13.6.2d Spa pump factor (FS) (kW/100 litres.annum)
Spa pump GEMS star rating
ACT
NSW
NT
Qld
SA
Tas
Vic
WA
All types
0.067
0.071
0.033
0.055
0.081
0.073
0.058
0.075
Tables
- Table 13.6.2a Floor area adjustment factor
- Table 13.6.2b Energy factor (EF)
- Table 13.6.2c Swimming pool pump factor (FP) (kW/1000 litres.annum)
- Table 13.6.2d Spa pump factor (FS) (kW/100 litres.annum)
Changed since NCC 2022 (minor wording). See ABCB Housing Provisions 2022 13.6.2, or show what changed.
(1) The net equivalent energy usage of a building, calculated … [formula] = the energy factor obtained from in Table 13.6.2b. (2) The swimming pool pump energy usage (EP) must be determined … = the swimming pool pump factor as per Table 13.6.2c. (3) The spa pump energy usage (ES) must be determined in … All types 0.067 0.071 0.033 0.055 0.081 0.073 0.058 0.075
Removed words are struck through; added words are highlighted. Comparison of the text only.