Housing Provisions clause · ABCB Housing Provisions 2022

13.6.2 Net equivalent energy usage

Part 13.6 Whole-of-home energy usage

Open 13.6.2 on NCC Online ↗

(1) The net equivalent energy usage of a building, calculated in accordance with (a), must not exceed the allowance calculated in accordance with (b)—

[formula] , where—

[formula] = the floor area factor obtained by multiplying the total floor area of the building by the adjustment factor in Table 13.6.2a; and

[formula] = the main space conditioning and main water heater efficiency factor obtained from the ABCB Standard for Whole-of-Home Efficiency Factors; and

[formula] = the swimming pool pump energy usage in (2); and

[formula] = the spa pump energy usage in (3); and

[formula] = the installed capacity of on-site photovoltaics (kW); and

[formula] , where—

[formula] = the floor area factor obtained from multiplying the total floor area of the building by the adjustment factor in Table 13.6.2a; and

[formula] = the energy factor obtained from in Table 13.6.2b.

The swimming pool pump energy usage (EP) must be determined in accordance with the following formula: [formula] , where—

[formula] = the swimming pool pump energy usage; and

[formula] = the volume of the swimming pool to the nearest 1000 litres; and

[formula] = the swimming pool pump factor as per Table 13.6.2c.

The spa pump energy usage (ES) must be determined in accordance with the following formula: [formula] , where—

[formula] = the spa pump energy usage; and

[formula] = the volume of the spa to the nearest 100 litres; and

[formula] = the spa pump factor as per Table 13.6.2d.

Table 13.6.2a Floor area adjustment factor

Total floor area m2

Floor area factor

Total floor area m2

Floor area factor

Total floor area m2

Floor area factor

Total floor area m2

Floor area factor

<50

0.0123

160–169

0.0097

280–289

0.0087

400–409

0.0080

50–59

0.0119

170–179

0.0096

290–299

0.0086

410–419

0.0079

60–69

0.0116

180–189

0.0095

300–309

0.0085

420–429

0.0079

70–79

0.0113

190–199

0.0094

310–319

0.0085

430–439

0.0078

80–89

0.0111

200–209

0.0093

320–329

0.0084

440–449

0.0078

90–99

0.0108

210–219

0.0092

330–339

0.0083

450–459

0.0077

100–109

0.0106

220–229

0.0091

340–349

0.0083

460–469

0.0077

110–119

0.0105

230–239

0.0090

350–359

0.0082

470–479

0.0077

120–129

0.0103

240–249

0.0090

360–369

0.0082

480–489

0.0076

130–139

0.0101

250–259

0.0089

370–379

0.0081

490–499

0.0076

140–149

0.0100

260–269

0.0088

380–389

0.0081

500

0.0075

150–159

0.0099

270–279

0.0087

390–399

0.0080

—

—

Table Notes

The total floor area is measured within the inside face of the external walls of the Class 1 building and includes any conditioned, attached Class 10a building.

Where values fall between ranges given, the floor area must be rounded up to the nearest whole square metres of floor area.

Table 13.6.2b Energy factor (EF)

Climate zone

ACT

NSW

NT

Qld

SA

Tas

Vic

WA

1

—

—

1.91

2.77

—

—

—

3.25

2

—

1.32

—

1.78

—

—

—

—

3

—

—

1.23

2.46

—

—

—

2.87

4

—

1.80

—

—

1.86

—

1.25

2.34

5

—

1.75

—

2.28

1.79

—

—

2.35

6

—

2.40

—

—

2.51

—

1.63

3.20

7

2.56

2.33

—

—

—

3.08

1.62

—

8

—

3.99

—

—

—

3.92

2.82

—

Table 13.6.2c Swimming pool pump factor (FP) (kW/1000 litres.annum)

Pool pump GEMS star rating

ACT

NSW

NT

Qld

SA

Tas

Vic

WA

1 or unrated

0.056

0.060

0.028

0.046

0.068

0.061

0.049

0.063

1.5

0.048

0.050

0.023

0.039

0.057

0.052

0.041

0.053

2

0.041

0.044

0.020

0.034

0.050

0.045

0.036

0.046

2.5

0.037

0.039

0.018

0.030

0.044

0.040

0.032

0.041

3

0.033

0.035

0.016

0.027

0.039

0.035

0.028

0.036

3.5

0.029

0.031

0.014

0.024

0.035

0.032

0.025

0.033

4

0.026

0.028

0.013

0.021

0.032

0.029

0.023

0.029

4.5

0.024

0.025

0.012

0.019

0.029

0.026

0.021

0.027

5

0.022

0.023

0.011

0.018

0.026

0.023

0.019

0.024

5.5

0.020

0.021

0.010

0.016

0.023

0.021

0.017

0.022

6

0.018

0.019

0.009

0.014

0.021

0.019

0.015

0.020

6.5

0.016

0.017

0.008

0.013

0.019

0.017

0.014

0.018

7

0.014

0.015

0.007

0.012

0.017

0.016

0.012

0.016

7.5

0.013

0.013

0.006

0.010

0.015

0.014

0.011

0.014

8

0.011

0.012

0.006

0.009

0.014

0.012

0.010

0.013

8.5

0.010

0.011

0.005

0.008

0.012

0.011

0.009

0.011

9

0.009

0.009

0.004

0.007

0.011

0.010

0.008

0.010

9.5

0.008

0.008

0.004

0.006

0.009

0.008

0.007

0.009

10

0.007

0.007

0.003

0.005

0.008

0.007

0.006

0.007

Table 13.6.2d Spa pump factor (FS) (kW/100 litres.annum)

Spa pump GEMS star rating

ACT

NSW

NT

Qld

SA

Tas

Vic

WA

All types

0.067

0.071

0.033

0.055

0.081

0.073

0.058

0.075

Tables

Changed in NCC 2025 (minor wording). See ABCB Housing Provisions 2025 13.6.2, or show what changed.

(1) The net equivalent energy usage of a building, calculated … [formula] = the energy factor obtained from in Table 13.6.2b. (2) The swimming pool pump energy usage (EP) must be determined … = the swimming pool pump factor as per Table 13.6.2c. (3) The spa pump energy usage (ES) must be determined in … All types 0.067 0.071 0.033 0.055 0.081 0.073 0.058 0.075

Removed words are struck through; added words are highlighted. Comparison of the text only.

Defined terms used