Housing Provisions clause · ABCB Housing Provisions 2025

5.3.3 External walls

Part 5.3 Cavity masonry

Open 5.3.3 on NCC Online ↗

(1) Cavity masonry walls must comply with the relevant provisions of this Part and Parts 5.6 and 5.7, and be constructed as follows:

The height of the wall between lateral supports (floor or ceiling or roof diaphragm) must be not more than 3 m.

Cavity masonry walls subject to wind loads must be supported by masonry cross walls or by steel mullions complying with (3).

Masonry cross walls must be—

not less than 2 m in length; and

at not more than 5.1 m centres where the length of the cavity wall being supported does not contain any opening or control joint; and

not more than 2.5 m from the edge of a control joint in the length of the cavity wall being supported; and

not more than a distance from the edge of an opening in the length of the cavity wall being supported as stated in Table 5.3.3; and

located at both edges of openings of width greater than 2.7 m; and

directly connected to the internal leaf of the cavity wall being supported using—

properly bonded units with at least 90 mm engagement on each side of the interface with the selected bond pattern but not less than every fourth course of masonry; or

medium duty Type A cavity wall ties in aligning mortar bed joints at a vertical spacing of not more than 300 mm; and

connected by a floor or ceiling diaphragm to the wall being supported where floor or ceiling connections are designed in accordance with AS/NZS 4600, AS 1720.1 or AS 3600, as appropriate.

(2) Cavity masonry walls must be constructed of two leaves, with each leaf not less than 90 mm wide.

(3) In cavity masonry construction, a cavity must be provided between the inner and outer masonry leaves as follows:

The cavity must be not less than 35 mm and not more than 75 mm in width, in accordance with 5.7.2.

Except for steel mullions, the minimum cavity width specified in (a) is to be maintained between the outer masonry leaf and any insulation or services located in the cavity.

Where steel mullions are located in a cavity as permitted by (b), a vertical damp-proof course must be placed between the outer masonry leaf and the mullion to prevent moisture penetration.

Table 5.3.3 Spacing of return walls for cavity walls with openings — distance from the edge of an opening (mm)

Wind class

Opening width (mm)

900

1500

2100

2700

N3

2100

1800

800

400

N2

3200

2900

2600

2300

N1

2500(Note)

2200(Note)

1900(Note)

800(Note)

Table Notes

The spacing in wind class N1 is smaller than for N2 because 5.6.5 states that for cavity walls in wind class N1, light duty cavity ties are to be used. This results in only relying on one leaf to resist the load instead of sharing it equally as per clause 7.7.3 of AS 3700.

Tables

Same wording in ABCB Housing Provisions 2022. See ABCB Housing Provisions 2022 5.3.3.