5.6.5 Wall ties
Part 5.6 Masonry components and accessories · NCC 2019: 3.3.5.10
Masonry wall ties must—
comply with AS 2699.1 and—
for masonry veneer walls be—
a minimum of light duty veneer ties in areas where the design wind speed is not more than N2; and
a minimum of medium duty veneer ties in areas where the design wind speed is more than N2; and
for cavity masonry walls be—
a minimum of light duty cavity ties in areas where the design wind speed is N1; and
a minimum of medium duty cavity ties in areas where the design wind speed is more than N1; and
where non-engaged piers are provided, piers must be tied to walls using medium duty ties; and
for monolithic or solid masonry construction be a minimum of medium duty ties; and
be spaced and fixed in accordance with Tables 5.6.5a, 5.6.5b and 5.6.5c (see also Figures 5.6.5a and 5.6.5b); and
be protected against corrosion in accordance with Table 5.6.5d.
Table 5.6.5a Wall tie spacings in masonry veneer
Direction
Wall tie spacing
450 mm wall stud spacing
600 mm wall stud spacing
Horizontal
Maximum 450 mm
Maximum 600 mm
Vertical
Maximum 600 mm
Maximum 400 mm
Table Notes
Wall ties that are suitable for higher duties are also suitable for use in lower duty conditions.
Table 5.6.5b Wall tie spacing in cavity and solid masonry
Direction
Wall tie spacing (maximum)
Cavity masonry
Solid or monolithic masonry
Horizontal
600 mm
400 mm
Vertical
600 mm
400 mm
Table Notes
Wall ties that are suitable for higher duties are also suitable for use in lower duty conditions.
Table 5.6.5c Placement of wall ties
Location
Placement of wall ties
Unsupported panel sides and edges of openings
Within 300 mm of panel side or edge
Top of veneer panels and top of panels under openings
Within 300 mm or two courses (whichever is the lesser) of the top of veneer
Bottom of veneer panel in masonry rebate sealed with liquid applied damp-proof course
Within 300 mm or two courses (whichever is the lesser) from the bottom of the veneer
Bottom of veneer panel supported on steel lintel
Bottom of veneer panel in masonry rebate with membrane damp-proof course
In each of the first two courses
Intersection of internal walls and external walls
350 mm vertically or 3-4 courses
Where articulation joints occur
At both sides of the articulation joint within 300 mm from the joint
Engaged piers
Within 200 mm of the top of the pier
Table Notes
Ties to be embedded a minimum of 50 mm into each masonry leaf.
Masonry wall ties must be installed in such a manner as to prevent moisture travelling along the tie to the inner leaf of masonry or the frame.
Table 5.6.5d Corrosion protection for wall ties
Exposure condition
Tie specification (minimum corrosion protection)
Areas less than 1km from breaking surf; or less than 100 m from salt water not subject to breaking surf; or within heavy industrial areas.
Grade 316L stainless steel; or engineered polymer complying with the requirements of AS 2699.1.
Areas 1km or more but less than 10km from breaking surf; or 100m or more but less than 1km from salt water not subject to breaking surf.
Sheet steel and bar ties galvanised after manufacture - 470 g/m2 on each side; or galvanised wire ties - 470 g/m2 coating mass; or Grade 304L stainless steel.
All other areas
Galvanised sheet steel - 300 g/m2 coating on each side; or sheet steel ties galvanised after manufacture - 300 g/m2 on each side.
Figure 5.6.5a Wall tie details (lowset)
Figure 5.6.5b Wall tie details (highset)
Figure Notes
Where wall ties are required, they must be placed in adjacent courses (as shown) or must be placed in the same course on each side of the stud.
Tables
- Table 5.6.5a Wall tie spacings in masonry veneer
- Table 5.6.5b Wall tie spacing in cavity and solid masonry
- Table 5.6.5c Placement of wall ties
- Table 5.6.5d Corrosion protection for wall ties