5.6.6 Fixing straps and tie-down systems

Part 5.6 Masonry components and accessories

Open 5.6.6 on NCC Online ↗

(1) Timber door and window frames abutting cavity masonry must be fixed with 300 mm long 30 mm x 0.8 mm kinked galvanised steel straps—

fixed to the back of frames; and

set into courses not less than 150 mm at not more than 400 mm intervals.

(2) For areas with a wind class of N1 or N2 and a building width from outside wall to outside wall of not more than 10 m in the direction of the roof span (see Figure 5.6.6a), sheet metal and tiled roofs must be tied down using one of the following methods:

30 mm x 0.8 mm galvanised steel straps at not more than 1.2 m centres and corresponding with truss or rafter positions, looped around 10 mm diameter galvanised mild steel rods—

built-in across the cavity at a course not less than 900 mm below the top of the wall; and

embedded not less than 50 mm into each leaf.

30 mm x 1 mm galvanised steel straps at not more than 1.2 m centres and corresponding with truss or rafter positions, built-in to masonry inner leaf not less than 50 mm and at a course not less than 900 mm below the top of the wall (see Figure 5.6.6b).

(3) Roof framing supporting tiled roofs on single leaf unreinforced masonry walls with engaged piers or return walls must have—

a built-in 30 mm x 0.8 mm galvanised steel strap fixed to the roof structure that extends the full height of the engaged pier or return wall; and

a 4.6 grade M12 galvanised steel rod which is cast into the footing when poured and looped and fixed around the galvanised steel strap required by (a) (see Figure 5.6.6c).

(4) Roof framing supporting sheet roofs on single leaf unreinforced masonry with engaged piers or return walls must have—

a built-in 30 mm x 0.8 mm galvanised steel strap fixed to the roof structure extending the full height of the engaged pier or return wall which is looped and fixed around a 4.6 grade 16 mm diameter galvanised steel rod cast into the footing when poured; or

a 4.6 grade M16 galvanised steel rod cast into the footing, threaded at the top and extending the full height of the pier or return wall to connect to the roof structure.

Figure 5.6.6a Building width

Figure 5.6.6b Suitable tie-down strap details for cavity masonry

Figure 5.6.6c Typical tie-down to single leaf unreinforced masonry

Same wording in ABCB Housing Provisions 2022. See ABCB Housing Provisions 2022 5.6.6.