Part 5.6 Masonry components and accessories
15 clauses · Open on NCC Online ↗
- 5.6.1 ApplicationPart 5.6 is subject to the limitations set out in H1D5(6)(c)(i), (ii) and (iii). (2) Part 5.6 need not be complied with if H1D5(6)(a) or (b) are…
- 5.6.2 Masonry unitsMasonry veneer masonry units must have a minimum compressive strength of— 3 MPa for solid or cored units; or 10 MPa for hollow units. (2) Cavity…
- Table 5.6.3 Acceptable mortar mixesMasonry unit exposure classification | Mortar mix by volume Note 1 Cement: lime: sand General use | Suitable for concrete masonry Note 2 Protected |…
- 5.6.3 Mortar mixesMortar used for masonry construction must comply with AS 3700 or AS 4773 except that the mortar may be mixed by volume in the proportions stated in…
- 5.6.4 Mortar jointsUnless otherwise specified, masonry bed and perpend joints must have a nominal thickness of 10 mm. (2) Raked joints are not to be used in saline…
- Table 5.6.5a Wall tie spacings in masonry veneerDirection | Wall tie spacing 450 mm wall stud spacing | 600 mm wall stud spacing Horizontal | Maximum 450 mm | Maximum 600 mm Vertical | Maximum 600…
- Table 5.6.5b Wall tie spacing in cavity and solid masonryDirection | Wall tie spacing (maximum) Cavity masonry | Solid or monolithic masonry Horizontal | 600 mm | 400 mm Vertical | 600 mm | 400 mm Table…
- Table 5.6.5c Placement of wall tiesLocation | Placement of wall ties Unsupported panel sides and edges of openings | Within 300 mm of panel side or edge Top of veneer panels and top…
- Table 5.6.5d Corrosion protection for wall tiesExposure condition | Tie specification (minimum corrosion protection) Areas less than 1km from breaking surf; or less than 100 m from salt water not…
- 5.6.5 Wall tiesMasonry wall ties must— comply with AS 2699.1 and— for masonry veneer walls be— a minimum of light duty veneer ties in areas where the design wind…
- 5.6.6 Fixing straps and tie-down systemsTimber door and window frames abutting cavity masonry must be fixed with 300 mm long 30 mm x 0.8 mm kinked galvanised steel straps— fixed to the…
- Table 5.6.7a Masonry lintel sizesLintel | Maximum clear span of lintel (mm): ≤ 600 mm of masonry over opening | Maximum clear span of lintel (mm): > 600 mm of masonry over opening…
- Table 5.6.7b Corrosion protection – LintelsDurability class of lintel in accordance with AS 2699.3 Note 1 | Material or protective requirements in accordance with AS 2699.3 Note 1 R1, R2 |…
- 5.6.7 LintelsWhere a lintel is required it must comply with the following: Steel lintels must comply with this Part or H1D6(3). Steel lintels must— be sized in…
- 5.6.8 Vertical articulation jointsVertical articulation joints must be provided in masonry walls in accordance with (2), except in walls constructed on sites where the soil…