5.6.7 Lintels

Part 5.6 Masonry components and accessories · NCC 2019: 3.3.5.12

Open 5.6.7 on NCC Online ↗

Where a lintel is required it must comply with the following:

Steel lintels must comply with this Part or H1D6(3).

Steel lintels must—

be sized in accordance with Table 5.6.7a; and

be installed with the long leg of lintel angle vertical; and

be wide enough so that the masonry does not overhang the horizontal leg of the lintel by more than 25 mm; and

not support masonry more than 3 m in height when measured above the opening; and

have a minimum bearing length at each end of the lintel of—

for clear spans not more than 1 m - 100 mm; or

for clear spans more than 1 m - 150 mm (See Figure 5.6.7); and

have a minimum of three courses of masonry over openings; and

comply with the corrosion protection requirements of Table 5.6.7b.

Table 5.6.7a Masonry lintel sizes

Lintel

Maximum clear span of lintel (mm): ≤ 600 mm of masonry over opening

Maximum clear span of lintel (mm): > 600 mm of masonry over opening

Flat 75 x 8

700

700

Flat 100 x 10

900

900

Angle 90 x 90 x 6EA

3000

2650

Angle 90 x 90 x 8EA

3200

2800

Angle 100 x 100 x 6EA

3350

2900

Angle 100 x 100 x 8EA

3600

3040

Angle 150 x 90 x 8UA

4200

3850

Table Notes

The lintels described in this Table must be not less than grade 300 MPa in accordance with AS 4100.

Table 5.6.7b Corrosion protection – Lintels

Durability class of lintel in accordance with AS 2699.3 Note 1

Material or protective requirements in accordance with AS 2699.3 Note 1

R1, R2

Hot dip galvanised with a minimum average coating thickness of 300 g/m2; or stainless steel 316L

R3

Hot dip galvanised with a minimum average coating thickness of 600 g/m2; or stainless steel 316L

R4

Stainless steel 316L

Table Notes

AS 2699.3 contains information on the corrosivity category locations in Australia and provides a method for determining coating thickness for lintels.

Additional decorative coatings can be applied, but must not be considered for the purpose of satisfying the requirements of this Table.

Any lintel with a coating that is modified, i.e. by cutting, welding, or where damaged, must have the coating restored to provide an equivalent level of protection provided by the original coating.

Figure 5.6.7 Lintel installation