5.7.4 Damp-proof courses and flashings – installation
Part 5.7 Weatherproofing of masonry · NCC 2019: 3.3.5.8
(1) Damp-proof courses and flashings must be—
located so as to form a continuous damp-proofing barrier—
around the bottom perimeter of walls where constructed on a concrete slab; and
in walls and piers below suspended floors; and
where a masonry wall passes through a roof; and
where a roof abuts an external masonry wall; and
to the bottom and tops of windows and doors and the like in accordance with (3), except a damp-proof course or a flashing need not be provided to the top of a window or door where the opening is protected by an eave of a width more than 3 times the height of the masonry veneer above the opening; and
continuous through the wall or pier and be visible from the outside face of the wall.
(2) The location of a damp-proof course, or flashing serving as a damp-proof course, must be not less than—
150 mm above the adjacent ground level; or
75 mm above the finished surface level of adjacent paved, concreted or landscaped areas that slope away from the wall; or
50 mm above finished paved, concreted or landscaped areas complying with 3.3.3(b)(ii) and protected from the direct effects of the weather by a carport, verandah or the like; or
in low rainfall intensity areas —
15 mm above finished paved, concreted or landscaped areas; or
0 mm above finished paved, concreted or landscaped areas if the damp-proof course is protected from the direct effects of the weather by a carport, verandah or the like.
(3) Sill and head flashings serving openings must be—
installed so that the flashing extends not less than 150 mm beyond the reveals on each side of the opening; and
located not more than—
one course below the sill brick course; and
300 mm above the opening; and
turned up in the cavity not less than 150 mm above the opening; and
embedded not less than 30 mm into—
for masonry veneer, the masonry leaf; and
for cavity masonry, the outer masonry leaf; and
attached to the window or wall framing.