Housing Provisions clause · ABCB Housing Provisions 2025
5.7.5 Weepholes
Part 5.7 Weatherproofing of masonry · NCC 2019: 3.3.5.9
(1) Except where excluded by (2), open perpend joints (weepholes) must be created in the course immediately above any flashing (including above any damp-proof course acting as a flashing) and be—
a minimum of 50 mm in height, by the width of the vertical mortar joint; and
at not more than 1.2 m centres; and
(2) Weepholes are not required in the following locations:
Where head openings are less than 1.2 m wide.
Beneath window and door sills.
Where the level of the external impervious surface is elevated for the purpose of providing step-free access required by H8P1.
Same wording in ABCB Housing Provisions 2022. See ABCB Housing Provisions 2022 5.7.5.