6.2.1 Subfloor ventilation
Part 6.2 Subfloor ventilation · NCC 2019: 3.4.1.2
(1) Subfloor spaces must—
be provided with openings in external walls and internal subfloor walls in accordance with Table 6.2.1a for the climatic zones given in Figure 6.2.1a; and
have clearance between the ground surface and the underside of the lowest horizontal member in the subfloor in accordance with Table 6.2.1b (see Figure 6.2.1b and Figure 6.2.1c).
(2) In addition to (1), a subfloor space must—
be cleared of all building debris and vegetation; and
have the ground beneath the suspended floor graded in accordance with 3.3.3; and
contain no dead air spaces; and
have openings evenly spaced as far as practicable (see Figure 6.2.1d); and
have openings placed not more than 600 mm in from corners.
(3) In double leaf masonry walls, openings specified in (1) must be provided in both leaves of the masonry, with openings being aligned to allow an unobstructed flow of air (see Figure 6.2.1d).
(4) Openings in internal subfloor walls specified in (1) must have an unobstructed area equivalent to that required for the adjacent external openings (see Figure 6.2.1d).
(5) Where the ground or subfloor space is excessively damp or subject to frequent flooding, in addition to the requirements of (1) to (4)—
the subfloor ventilation required in (1) must be increased by 50%; or
the ground within the subfloor space must be sealed with an impervious membrane; or
subfloor framing must be—
where above ground — above ground durability Class 1 or 2 timbers or H3 preservative treated timbers in accordance with AS 1684.2, AS 1684.3 or AS 1684.4; or
where in-ground — in-ground durability Class 1 or 2 timbers or H5 preservative treated timbers in accordance with AS 1684.2, AS 1684.3 or AS 1684.4; or
steel in accordance with NASH Standard ‘Residential and Low-Rise Steel Framing’ Part 2.
Table 6.2.1a Subfloor openings
Climatic zone (see Figure 6.2.1a)
Minimum aggregate subfloor ventilation openings with no membrane (mm2/m of wall)
Minimum aggregate subfloor ventilation openings with ground sealed with impervious membrane (mm2/m of wall)
A
2000
1000
B
4000
2000
C
6000
3000
Table Notes
In situations where openings in external walls and internal subfloor walls, including separating walls, are not able to be provided, additional measures must be provided to ensure that the overall level of ventilation of the subfloor space is maintained. This may include measures similar to those in 6.2.1(5) i.e. providing durability class timbers, or having the ground sealed in the subfloor space with an impervious membrane.
Table 6.2.1b Ground clearance
Climatic zone (see Figure 6.2.1a)
Minimum ground clearance height where termite inspection or management system is not required (mm)
Minimum ground clearance height where termite inspection is required (mm)
A, B and C
150
400
Table Notes
400 mm clearance required only where termite management systems are installed that need to be inspected (see Part 2.2.4).
On sloping sites the 400 mm clearance required by (1) may be reduced to 150 mm within 2 m of external walls in accordance with Figure 6.2.1b.
Figure 6.2.1a Climatic zones based on relative humidity
Figure 6.2.1b Subfloor clearance requirements
Figure Notes
See notes to Tables 6.2.1a and 6.2.1b.
Figure 6.2.1c Subfloor clearance requirements – detail
Figure Notes
See notes to Tables 6.2.1a and 6.2.1b.
Figure 6.2.1d Typical subfloor ventilation details — typical cross ventilation of subfloor area
Tables
Clauses referred to
- 3.3.3 Surface water drainage
- 2.2.4 Determination of structural resistance of materials and forms of construction