Table 6.2.1b Ground clearance
| Climatic zone (see Figure 6.2.1a) | Minimum ground clearance height where termite inspection or management system is not required (mm) | Minimum ground clearance height where termite inspection is required (mm) |
|---|---|---|
| A, B and C | 150 | 400 |
Table Notes
400 mm clearance required only where termite management systems are installed that need to be inspected (see Part 2.2.4).
On sloping sites the 400 mm clearance required by (1) may be reduced to 150 mm within 2 m of external walls in accordance with Figure 6.2.1b.
Table for 6.2.1 Subfloor ventilation
Same wording in ABCB Housing Provisions 2022. See ABCB Housing Provisions 2022 Table 6.2.1b.