Housing Provisions clause · ABCB Housing Provisions 2025

6.3.7 Fixings and bearing for structural steel members

Part 6.3 Structural steel members

Open 6.3.7 on NCC Online ↗

(1) All bolts used in connections must be hot dip galvanised 300 g/m2.

(2) Bearer connections must be fixed in accordance with Figure 6.3.7a.

(3) Joists, bearers and lintels must be restrained from lateral movement or twisting along their length by fixing rafters or joists to the top flange of the member so as to prevent the member from moving laterally.

(4) End supports for bearers and lintels must transfer loads to the footings and have a bearing distance as follows:

For single spans, the bearing distance must be not less than the width of the member.

For continuous spans, internal bearing must be not less than two times the width of the member.

(5) Strutting beams must—

be supported and fixed in accordance with Figure 6.3.7b; and

where ends are cut to suit roof pitch, be cut in accordance with Figure 6.3.7c.

(6) Lintels must be fixed in accordance with Figures 6.3.7d, 6.3.7e, 6.3.7f, 6.3.7g and 6.3.7h.

Figure 6.3.7a Bearer supporting a timber floor and non-loadbearing stud wall

Figure 6.3.7b Strutting beam supporting roof and ceiling

Figure 6.3.7c End cuts to strutting beams

Figure Notes

Strutting beam top plate to be tied down in accordance with 6.3.4.

Figure 6.3.7d Lintels supporting roof, frames and timber floors

Figure 6.3.7e Lintels supporting roof, frames and timber floors — sections

Figure 6.3.7f Typical universal beam to column connection detail

Figure Notes

8 mm steel plates to be welded to the top and bottom of the column using 5 mm fillet welds.

Plate width must be the greater of the column width or the beam width.

Plate length must be such that there is not less than 40 mm from the centreline of the bolts to the ends.

All bolting between structural steel members must be not less than 2 M12 4.6/S.

Figure 6.3.7g Typical PFC and RHS beam to column connection detail

Figure 6.3.7h Typical column base plate detail

Figure Notes

Fixing of the column base plate to the slab must be not less than 2 M12 4.6/S post-installed mechanical anchors.

Same wording in ABCB Housing Provisions 2022. See ABCB Housing Provisions 2022 6.3.7.