6.3.6 Columns
Part 6.3 Structural steel members · NCC 2019: 3.4.4.3
Structural steel columns must comply with the following:
Columns must support the maximum area provided for in—
Tables 6.3.6a, 6.3.6b and 6.3.6c for columns supporting tiled floor and tiled roof load; and
Tables 6.3.6d, 6.3.6e and 6.3.6f for columns supporting timber floor and metal roof load.
The floor area to be supported is to be determined in accordance with Table 6.3.6g and Figure 6.3.6a.
The flooring system supported by structural steel columns must be fully braced to the footing level either by—
subject to (d), adequately fixing the full height of the column to bracing walls of similar height in the two orthogonal directions of the building; or
a bracing system designed in accordance with AS 1684.2, AS 1684.3, AS/NZS 4600, NASH standard or AS 3700 as appropriate to the materials being used.
For the purposes of (c)(i), the bracing walls must be capable of resisting racking forces in each direction not less than a proportion of the building’s racking force equal to the proportion of floor area that the column is supporting compared to the total floor area of the building.
Acceptable load eccentricity must not exceed 50% of the cross-sectional width plus 100 mm (see Figure 6.3.6b).
Have a minimum nominal yield strength of 250 MPa.
Table 6.3.6a Required column section — columns supporting tiled floor and tiled roof load — roof load area = 0 m2
Column section
Effective height (mm)
Floor load area (m2)
4
10
16
CHS 250
2400
60.3 x 4.5 CHS
88.9 x 5 CHS
114.3 x 4.5 CHS
CHS 250
2700
60.3 x 4.5 CHS
88.9 x 5 CHS
114.3 x 4.5 CHS
CHS 250
3000
60.3 x 4.5 CHS
88.9 x 5 CHS
114.3 x 4.5 CHS
CHS 250
3300
60.3 x 5.4 CHS
88.9 x 5 CHS
114.3 x 5.4 CHS
CHS 250
3600
60.3 x 5.4 CHS
88.9 x 5 CHS
114.3 x 5.4 CHS
CHS 350
2400
60.3 x 2.9 CHS
88.9 x 3.2 CHS
114.3 x 3.2 CHS
CHS 350
2700
60.3 x 2.9 CHS
88.9 x 3.2 CHS
114.3 x 3.2 CHS
CHS 350
3000
60.3 x 2.9 CHS
88.9 x 3.2 CHS
114.3 x 3.2 CHS
CHS 350
3300
76.1 x 2.3 CHS
88.9 x 3.2 CHS
114.3 x 3.2 CHS
CHS 350
3600
76.1 x 2.3 CHS
101.6 x 2.6 CHS
114.3 x 3.2 CHS
SHS 350
2400
65 x 65 x 2 SHS
89 x 89 x 3.5 SHS
100 x 100 x 4 SHS
SHS 350
2700
65 x 65 x 2 SHS
89 x 89 x 3.5 SHS
100 x 100 x 4 SHS
SHS 350
3000
65 x 65 x 2 SHS
89 x 89 x 3.5 SHS
100 x 100 x 4 SHS
SHS 350
3300
65 x 65 x 2 SHS
89 x 89 x 3.5 SHS
100 x 100 x 4 SHS
SHS 350
3600
65 x 65 x 2.5 SHS
89 x 89 x 3.5 SHS
100 x 100 x 4 SHS
SHS 450
2400
50 x 50 x 2 SHS
89 x 89 x 3.5 SHS
100 x 100 x 3 SHS
SHS 450
2700
65 x 65 x 2 SHS
89 x 89 x 3.5 SHS
100 x 100 x 3 SHS
SHS 450
3000
65 x 65 x 2 SHS
89 x 89 x 3.5 SHS
100 x 100 x 3 SHS
SHS 450
3300
65 x 65 x 2 SHS
89 x 89 x 3.5 SHS
100 x 100 x 3 SHS
SHS 450
3600
65 x 65 x 2 SHS
89 x 89 x 3.5 SHS
100 x 100 x 3 SHS
Table Notes
Load accounted for includes 0.98 kPa permanent floor, 1.16 kN/m permanent wall, 0.85 kPa permanent roof, permanent member self-weight, 1.5 kPa or 1.1 kN imposed floor.
Load combinations included are 1.35G and 1.2G + 1.5Q for ULS.
Columns are assumed to be simply-supported at both ends with an effective length factor of 1.
A maximum load eccentricity of 100 mm has been accounted for in the columns.
A roof load area of “0” must be used for columns not supporting roof loads.
The length of wall load allowed for is equal to the square root of the floor area.
Table 6.3.6b Required column section — columns supporting tiled floor and tiled roof load — roof load area = 9 m2
Column section
Effective height (mm)
Floor load area (m2)
4
10
16
CHS 250
2400
76.1 x 4.5 CHS
101.6 x 5 CHS
114.3 x 5.4 CHS
CHS 250
2700
76.1 x 4.5 CHS
101.6 x 5 CHS
114.3 x 5.4 CHS
CHS 250
3000
76.1 x 5.9 CHS
101.6 x 5 CHS
139.7 x 5 CHS
CHS 250
3300
76.1 x 5.9 CHS
101.6 x 5 CHS
139.7 x 5 CHS
CHS 250
3600
76.1 x 5.9 CHS
101.6 x 5 CHS
139.7 x 5 CHS
CHS 350
2400
76.1 x 3.2 CHS
101.6 x 3.2 CHS
139.7 x 3 CHS
CHS 350
2700
76.1 x 3.2 CHS
101.6 x 3.2 CHS
139.7 x 3 CHS
CHS 350
3000
76.1 x 3.2 CHS
114.3 x 3.2 CHS
139.7 x 3 CHS
CHS 350
3300
88.9 x 2.6 CHS
114.3 x 3.2 CHS
139.7 x 3 CHS
CHS 350
3600
88.9 x 2.6 CHS
114.3 x 3.2 CHS
139.7 x 3 CHS
SHS 350
2400
89 x 89 x 3.5 SHS
100 x 100 x 3 SHS
100 x 100 x 4 SHS
SHS 350
2700
89 x 89 x 3.5 SHS
100 x 100 x 3 SHS
100 x 100 x 4 SHS
SHS 350
3000
89 x 89 x 3.5 SHS
100 x 100 x 3 SHS
100 x 100 x 4 SHS
SHS 350
3300
89 x 89 x 3.5 SHS
100 x 100 x 3 SHS
100 x 100 x 4 SHS
SHS 350
3600
89 x 89 x 3.5 SHS
100 x 100 x 3 SHS
100 x 100 x 4 SHS
SHS 450
2400
75 x 75 x 2.5 SHS
89 x 89 x 3.5 SHS
100 x 100 x 3 SHS
SHS 450
2700
75 x 75 x 2.5 SHS
89 x 89 x 3.5 SHS
100 x 100 x 3 SHS
SHS 450
3000
75 x 75 x 2.5 SHS
89 x 89 x 3.5 SHS
100 x 100 x 4 SHS
SHS 450
3300
75 x 75 x 2.5 SHS
89 x 89 x 3.5 SHS
100 x 100 x 4 SHS
SHS 450
3600
75 x 75 x 2.5 SHS
89 x 89 x 3.5 SHS
100 x 100 x 4 SHS
Table Notes
Load accounted for includes 0.98 kPa permanent floor, 1.16 kN/m permanent wall, 0.85 kPa permanent roof, permanent member self-weight, 1.5 kPa or 1.1 kN imposed floor and 0.25 kPa imposed roof.
Load combinations included are 1.35G and 1.2G + 1.5Q for ULS.
Columns are assumed to be simply-supported at both ends with an effective length factor of 1.
A maximum load eccentricity of 100 mm has been accounted for in the columns.
A roof load area of “0” must be used for columns not supporting roof loads.
The length of wall load allowed for is equal to the square root of the floor area.
Table 6.3.6c Required column section — columns supporting tiled floor and tiled roof load — roof load area = 18 m2
Column section
Effective height (mm)
Floor load area (m2)
4
10
16
CHS 250
2400
88.9 x 5 CHS
114.3 x 5.4 CHS
139.7 x 5 CHS
CHS 250
2700
88.9 x 5 CHS
114.3 x 5.4 CHS
139.7 x 5 CHS
CHS 250
3000
88.9 x 5 CHS
114.3 x 5.4 CHS
139.7 x 5 CHS
CHS 250
3300
88.9 x 5.9 CHS
114.3 x 5.4 CHS
139.7 x 5 CHS
CHS 250
3600
88.9 x 5.9 CHS
114.3 x 5.4 CHS
139.7 x 5 CHS
CHS 350
2400
101.6 x 2.6 CHS
114.3 x 3.6 CHS
139.7 x 3.5 CHS
CHS 350
2700
101.6 x 2.6 CHS
114.3 x 3.6 CHS
139.7 x 3.5 CHS
CHS 350
3000
101.6 x 3.2 CHS
114.3 x 3.6 CHS
139.7 x 3.5 CHS
CHS 350
3300
101.6 x 3.2 CHS
114.3 x 3.6 CHS
139.7 x 3.5 CHS
CHS 350
3600
101.6 x 3.2 CHS
114.3 x 3.6 CHS
139.7 x 3.5 CHS
SHS 350
2400
89 x 89 x 3.5 SHS
100 x 100 x 4 SHS
100 x 100 x 4 SHS
SHS 350
2700
89 x 89 x 3.5 SHS
100 x 100 x 4 SHS
100 x 100 x 4 SHS
SHS 350
3000
89 x 89 x 3.5 SHS
100 x 100 x 4 SHS
100 x 100 x 5 SHS
SHS 350
3300
100 x 100 x 3 SHS
100 x 100 x 4 SHS
100 x 100 x 5 SHS
SHS 350
3600
100 x 100 x 3 SHS
100 x 100 x 4 SHS
100 x 100 x 5 SHS
SHS 450
2400
89 x 89 x 3.5 SHS
100 x 100 x 3 SHS
100 x 100 x 4 SHS
SHS 450
2700
89 x 89 x 3.5 SHS
100 x 100 x 3 SHS
100 x 100 x 4 SHS
SHS 450
3000
89 x 89 x 3.5 SHS
100 x 100 x 3 SHS
100 x 100 x 4 SHS
SHS 450
3300
89 x 89 x 3.5 SHS
100 x 100 x 3 SHS
100 x 100 x 4 SHS
SHS 450
3600
89 x 89 x 3.5 SHS
100 x 100 x 3 SHS
100 x 100 x 4 SHS
Table Notes
Load accounted for includes 0.98 kPa permanent floor, 1.16 kN/m permanent wall, 0.85 kPa permanent roof, permanent member self-weight, 1.5 kPa or 1.1 kN imposed floor and 0.25 kPa imposed roof.
Load combinations included are 1.35G and 1.2G + 1.5Q for ULS.
Columns are assumed to be simply-supported at both ends with an effective length factor of 1.
A maximum load eccentricity of 100 mm has been accounted for in the columns.
A roof load area of “0” must be used for columns not supporting roof loads.
The length of wall load allowed for is equal to the square root of the floor area.
Table 6.3.6d Required column section — columns supporting timber floor and metal roof load — roof load area = 0 m2
Column section
Effective height (mm)
Floor load area (m2)
4
10
16
CHS 250
2400
60.3 x 3.6 CHS
76.1 x 5.9 CHS
101.6 x 5 CHS
CHS 250
2700
60.3 x 3.6 CHS
76.1 x 5.9 CHS
101.6 x 5 CHS
CHS 250
3000
60.3 x 4.5 CHS
76.1 x 5.9 CHS
101.6 x 5 CHS
CHS 250
3300
60.3 x 4.5 CHS
76.1 x 5.9 CHS
101.6 x 5 CHS
CHS 250
3600
60.3 x 4.5 CHS
88.9 x 5 CHS
101.6 x 5 CHS
CHS 350
2400
60.3 x 2.3 CHS
88.9 x 2.6 CHS
101.6 x 3.2 CHS
CHS 350
2700
60.3 x 2.9 CHS
88.9 x 2.6 CHS
114.3 x 3.2 CHS
CHS 350
3000
60.3 x 2.9 CHS
88.9 x 3.2 CHS
114.3 x 3.2 CHS
CHS 350
3300
60.3 x 2.9 CHS
88.9 x 3.2 CHS
114.3 x 3.2 CHS
Tables
- Table 6.3.6a Required column section — columns supporting tiled floor and tiled roof load — roof load area = 0 m2
- Table 6.3.6b Required column section — columns supporting tiled floor and tiled roof load — roof load area = 9 m2
- Table 6.3.6c Required column section — columns supporting tiled floor and tiled roof load — roof load area = 18 m2
- Table 6.3.6d Required column section — columns supporting timber floor and metal roof load — roof load area = 0 m2
- Table 6.3.6e Required column section — columns supporting timber floor and metal roof load — roof load area = 9 m2
- Table 6.3.6f Required column section — columns supporting timber floor and metal roof load — roof load area = 18 m2
- Table 6.3.6g Area supported by columns