9.2.9 Allowable encroachments
Part 9.2 Fire separation of external walls · NCC 2019: SA 3.7.2.7, 3.7.2.7
(1) An encroachment is any construction—
between the external wall of the building and the allotment boundary other than a boundary adjoining a road or other public space; or
between the external walls of two buildings on the same allotment; or
between the external wall of the building and the vertical projection of the external wall of another building on the same allotment; or
that extends beyond the vertical projection of another building on the same allotment other than a building it is associated with.
(2) For the purposes of (1), an encroachment relates to any external wall of—
a Class 10a building required to comply with 9.2.4; or
a Class 1 building.
(3) Encroachments allowed within 900 mm of an allotment boundary or within 1.8 m of another building, or its vertical projection, on the same allotment are—
non-combustible fascias, gutters and downpipes; and
light fittings, electricity or gas meters, aerials or antennas; and
pergolas, sun blinds or water tanks (see Figure 9.2.9a); and
unroofed terraces, landings, steps and ramps, not more than 1 m in height; and
open carports that comply with 9.2.8.
(4) Encroachments allowed up to but not closer than 450 mm from an allotment boundary or up to but not closer than 900 mm from another building, or its vertical projection, on the same allotment or associated encroachments of another building on the same allotment are—
combustible fascias, gutters and downpipes (see Figure 9.2.9a, Figure 9.2.9b and Figure 9.2.9c); and
eaves with non-combustible roof cladding and non-combustible lining; and
flues, chimneys, pipes, domestic fuel tanks, cooling or heating appliances or other services.
(5) Encroachments allowed to project beyond the vertical projection of another building on the same allotment are non-combustible fascias, gutters and downpipes (see Figure 9.2.3b).
Figure 9.2.9a Allowable encroachments for non-combustible construction — Combustible fascia up to but not closer than 450 mm to an allotment boundary
Figure 9.2.9b Allowable encroachments for non-combustible construction — Non-combustible fascia and gutter within 900 mm of an allotment boundary
Figure 9.2.9c Allowable encroachments for non-combustible construction — Unroofed pergola within 900 mm of an allotment boundary
Changed since NCC 2022. See ABCB Housing Provisions 2022 9.2.9, or show what changed.