Housing Provisions clause · ABCB Housing Provisions 2025

9.5.2 Location – Class 1a buildings

Part 9.5 Smoke alarms and evacuation lighting · NCC 2019: 3.7.5.3

Open 9.5.2 on NCC Online ↗

In a Class 1a building, smoke alarms must be located in—

any storey containing bedrooms, every corridor or hallway associated with a bedroom, or if there is no corridor or hallway, in an area between the bedrooms and the remainder of the building; and

each other storey not containing bedrooms.

Notes

Figure 9.5.2a and 9.5.2b illustrates requirements of this provision.

Figure 9.5.2a Class 1a building where all bedrooms are grouped together and served by a hallway

Figure Notes

In this diagram, the location of the smoke alarm is indicated by a black dot.

Figure 9.5.2b Class 1a building where bedrooms are located in separate areas

Figure Notes

In this diagram, the location of each smoke alarm is indicated by a black dot.

Smoke alarms are required to be interconnected by 9.5.1(d).

Same wording in ABCB Housing Provisions 2022. See ABCB Housing Provisions 2022 9.5.2.

Clauses referred to

Defined terms used