Housing Provisions clause · ABCB Housing Provisions 2025
9.5.1 Smoke alarm requirements
Part 9.5 Smoke alarms and evacuation lighting · NCC 2019: NSW 3.7.5.2 and NSW 1.1.4, 3.7.5.2
Varied in NSW. Check the variation for your state.
Smoke alarms must—
be located in—
a Class 1a building in accordance with 9.5.2 and 9.5.4; and
a Class 1b building in accordance with 9.5.3 and 9.5.4; and
comply with AS 3786, except that in a Class 10a private garage where the use of the area is likely to result in smoke alarms causing spurious signals, any other alarm deemed suitable in accordance with AS 1670.1 may be installed provided that smoke alarms complying with AS 3786 are installed elsewhere in the Class 1 building; and
be powered from the consumer mains source where a consumer mains source is supplied to the building; and
be interconnected where there is more than one alarm.
Same wording in ABCB Housing Provisions 2022. See ABCB Housing Provisions 2022 9.5.1.
State and territory variations all clauses side by side →
Clauses referred to
- 9.5.2 Location – Class 1a buildings
- 9.5.4 Installation of smoke alarms
- 9.5.3 Location – Class 1b buildings