NSW 9.4.3 Construction of walls
NSW Part 9.4 Fire protection of garage top dwellings
Insert NSW clause 9.4.3 in clause 9.4.3 as follows:
(1) A wall required by NSW 9.4.1(2) or NSW 9.4.1(3)(a) must—
have an FRL of not less than 30/30/30 when tested from the non-associated private garage side; or
be of masonry construction not less than 90 mm thick.
(2) A wall subject to (1) must—
commence at the footings or ground slab; and
extend to the underside of a floor complying with NSW 9.4.2.
(3) A wall referred to in (1)(a), if of lightweight construction must be tested in accordance with Specification 6 of Volume One.
(4) Where a service passes through a wall referred to in (1), the penetration must not reduce the performance of the wall.
(5) A wall required by NSW 9.4.1(2) or NSW 9.4.1(3)(a) need not comply with 9.3.1.