NT 13.5.2 Air movement
NT Part 13.5 Ceiling fans · varies 13.5.2 Ceiling fans
Insert NT clause 13.5.2 in clause 13.5.2 as follows:
(1) Air movement must be provided to habitable rooms in accordance with Table NT 13.5.2.
(2) Air movement required by (1) may be provided through an opening from an adjoining room (including an enclosed verandah) if—
the adjoining room is not a sanitary compartment; and
the opening between the adjoining room and the habitable room complies with Table NT 13.5.2 as if it were a ventilation opening to the habitable room or a proportion there of if some ventilation is provided from another source; and
the ventilation opening to the adjoining room complies with Table NT 13.5.2 for the total area of the floor of the adjoining room and the proportion of the habitable room that is ventilated from the adjoining room.
Insert NT table (13.5.2) 13.5.2 as follows:
NT Table 13.5.2: Minimum total ventilation opening area as a percentage of the floor area for each habitable room
Climate zone
Minimum total ventilation opening area per habitable room (percentage of the area of the floor of the habitable room)
Without a ceiling fan or evaporative cooler
With a ceiling fan
With an evaporative cooler
1
15%
12.5%
15%
3
12.5%
7.5%
7.5%
Changed since NCC 2022. See ABCB Housing Provisions 2022 NT 13.5.2, or show what changed.
Insert NT clause 13.5.2 in clause 13.5.2 as follows: (1) Air movement must be provided to habitable rooms in … evaporative cooler 1 15% 12.5% 15% 3 12.5% 7.5% 7.5%
Removed words are struck through; added words are highlighted. Comparison of the text only.