5.4.3 Internal walls

Part 5.4 Unreinforced single leaf masonry

Open 5.4.3 on NCC Online ↗

Internal masonry walls must be engaged with other walls, must comply with the relevant provisions of this Part and must be—

not less than 75 mm thick; and

supported by either—

the ceiling structure in accordance with Figure 5.4.3a; or

return walls in accordance with Figure 5.4.3b.

Figure 5.4.3a Support for internal walls — supported by ceiling structure

Figure Notes

Timber joist must be fixed to top plate in accordance with H1D6(4).

Fixing of top plate to masonry wall must be in accordance with 5.6.6.

Figure 5.4.3b Support for internal walls — supported by return walls

Figure Notes

An opening of not more than 600 mm x 900 mm is allowed to internal walls without additional support.

Openings larger than as described in Note 1 and door openings must be supported.

The maximum allowable height for the wall is described in Figure 5.4.3a.

Articulation joints must be in accordance with 5.6.8.

Same wording in ABCB Housing Provisions 2022. See ABCB Housing Provisions 2022 5.4.3.