Table 13.2.5t Lightweight metal-framed walls – thermal bridging mitigation
| Wall insulation R-Value from Tables 13.2.5a to 13.2.5o | Thermal bridging mitigation |
|---|---|
| 0 or reflective | Not required |
| >0 to ≤1.5 | Either install reflective insulation outside the frame to create a minimum 20 mm reflective airspace between frame and cladding, or increase insulation between frames by R0.5. |
| >1.5 | Either install reflective insulation outside the frame to create a minimum 20 mm reflective airspace between frame and cladding, or add a layer of continuous insulation with an R-Value of at least R0.30 on the inside or the outside of the frame. |
Table Notes
Minimum R-Value s are in-situ values. They account for compression of insulation.
The surface emittance of a reflective surface facing an airspace must be a maximum of 0.1.
Table for 13.2.5 External walls
Same wording in ABCB Housing Provisions 2022. See ABCB Housing Provisions 2022 Table 13.2.5t.