Table 13.3.2a Maximum conductance to solar heat gain ratio (CU/CSHGC)

Part 13.3 External glazing

Open Table 13.3.2a on NCC Online ↗
Climate zoneFloor in direct contact with the groundSuspended floor
29.609.37
319.1014.75
410.258.04
5 (lightweight wall)8.898.32
5 (concrete or masonry wall)8.7910.12
68.456.06
77.027.96
84.939.41

Table for 13.3.2 External glazing — winter