Table · ABCB Housing Provisions 2025
Table 13.3.2ad Winter solar heat gain factors: climate zone 5 — concrete or masonry wall
| Type of factor | Factor for a floor in direct contact with the ground | Factor for a suspended floor |
|---|---|---|
| Room factor (RW) for a bedroom and a room which is not a conditioned space | 0.40 | 0.30 |
| Bedroom solar heat gain factor (BSW) | 1.00 | 0.60 |
| Level factor (LW) for all floor levels above the lowest floor | 1.40 | 1.10 |
| Frame factor (FW) for frames with a solar absorptance of ≤ 0.40 | 0.97 | 0.90 |
| Frame factor (FW) for frames with a solar absorptance of > 0.40 to < 0.68 | 1.00 | 1.00 |
| Frame factor (FW) for frames with a solar absorptance of ≥ 0.68 | 1.04 | 1.00 |
| Floor factor (for tiled or vinyl covered floor) (HW) | 1.10 | Not applicable |
Table Notes
This Table only applies to dwellings with both high mass external and internal walls, for example masonry cavity walls and masonry internal walls.
Where a factor is listed as ‘Not applicable’, the value of the factor must be taken as 1.0.
Table for 13.3.2 External glazing — winter
Same wording in ABCB Housing Provisions 2022. See ABCB Housing Provisions 2022 Table 13.3.2ad.