Table 13.3.2f Orientation sector winter exposure factor (EW) — floor in direct contact with the ground: climate zone 4

Part 13.3 External glazing

Open Table 13.3.2f on NCC Online ↗
P/HNorthNorth eastEastSouth eastSouthSouth westWestNorth west
0.001.481.400.910.470.460.511.111.57
0.051.451.340.840.400.380.431.031.51
0.101.431.300.810.370.360.400.981.46
0.201.221.180.740.340.330.360.881.31
0.401.111.010.620.290.290.310.751.13
0.600.920.830.540.250.250.270.640.92
0.800.800.680.470.230.230.250.570.77
1.000.640.610.410.200.210.220.480.66
1.200.460.470.360.180.210.210.440.57
1.400.350,430.330.170.200.200.390.48
1.600.260.380.310.170.180.180.340.42
1.800.200.320.280.160.180.170.310.36
2.000.180.300.240.140.170.160.290.30

Table Notes

For P/H between those shown in this Table, either use the next highest P/H or interpolate.

Table for 13.3.2 External glazing — winter

Same wording in ABCB Housing Provisions 2022. See ABCB Housing Provisions 2022 Table 13.3.2f.