Table 4.2.20b Localised thickening under concentrated load — tiled floor and tiled roof — roof load area = maximum 9 m2
Part 4.2 Footings, slabs and associated elements
| Localised thickening | Maximum floor load area (m2) | ||
|---|---|---|---|
| 4 | 10 | 16 | |
| Square thickening size (mm) | 650 x 650 | 800 x 800 | 950 x 950 |
| Thickening depth (mm) | 350 | 400 | 450 |
Table Notes
Load accounted for includes 0.98 kPa permanent tiled floor, 0.85 kPa permanent tiled roof, 1.16 kN/m permanent wall, permanent member self-weight, 1.5 kPa or 1.1 kN imposed floor and 0.25 kPa imposed roof.
Load combinations included are G + 0.5Q for ULS.
Minimum bearing pressure is 100 kPa for pad footings.
The length of wall allowed for is equal to the square root of the floor area.
Table for 4.2.20 Concentrated loads
Changed since NCC 2022 (minor wording). See ABCB Housing Provisions 2022 Table 4.2.20b, or show what changed.