4.2.20 Concentrated loads
Part 4.2 Footings, slabs and associated elements
Where a footing or slab supports a concentrated load from a structural steel column, localised thickening must—
be provided in accordance with—
for tiled floor and tiled roof, Tables 4.2.20a, 4.2.20b or 4.2.20c; or
for timber floor and metal roof, Tables 4.2.20d, 4.2.20e or 4.2.20f; and
be centred under the structural steel column; and
have SL72 reinforcement with a minimum 50 mm of concrete cover (see Figure 4.2.20).
Table 4.2.20a Localised thickening under concentrated load — tiled floor and tiled roof — roof load area = 0 m2
Localised thickening
Maximum floor load area (m2)
4
10
16
Square thickening size (mm)
450 x 450
650 x 650
850 x 850
Thickening depth (mm)
250
350
400
Table Notes
Load accounted for includes 0.98 kPa permanent tiled floor, 0.85 kPa permanent tiled roof, 1.16 kN/m permanent wall, permanent member self-weight, 1.5 kPa or 1.1 kN imposed floor and 0.25 kPa imposed roof.
Load combinations included are G + 0.5Q for ULS.
Minimum bearing pressure is 100 kPa for pad footings.
A roof load area of “0” must be used for footings not supporting roof loads.
The length of wall allowed for is equal to the square root of the floor area.
Table 4.2.20b Localised thickening under concentrated load — tiled floor and tiled roof — roof load area = maximum 9 m2
Localised thickening
Maximum floor load area (m2)
4
10
16
Square thickening size (mm)
650 x 650
800 x 800
950 x 950
Thickening depth (mm)
350
400
450
Table Notes
Load accounted for includes 0.98 kPa permanent tiled floor, 0.85 kPa permanent tiled roof, 1.16 kN/m permanent wall, permanent member self-weight, 1.5 kPa or 1.1 kN imposed floor and 0.25 kPa imposed roof.
Load combinations included are G + 0.5Q for ULS.
Minimum bearing pressure is 100 kPa for pad footings.
The length of wall allowed for is equal to the square root of the floor area.
Table 4.2.20c Localised thickening under concentrated load — tiled floor and tiled roof — roof load area = maximum 18 m2
Localised thickening
Maximum floor load area (m2)
4
10
16
Square thickening size (mm)
750 x 750
900 x 900
1000 x 1000
Thickening depth (mm)
400
450
500
Table Notes
Load accounted for includes 0.98 kPa permanent tiled floor, 0.85 kPa permanent tiled roof, 1.16 kN/m permanent wall, permanent member self-weight, 1.5 kPa or 1.1 kN imposed floor and 0.25 kPa imposed roof.
Load combinations included are G + 0.5Q for ULS.
Minimum bearing pressure is 100 kPa for pad footings.
The length of wall allowed for is equal to the square root of the floor area.
Table 4.2.20d Localised thickening under concentrated load — timber floor and metal roof — roof load area = 0 m2
Localised thickening
Maximum floor load area (m2)
4
10
16
Square thickening size (mm)
400 x 400
600 x 600
750 x 750
Thickening depth (mm)
250
300
350
Table Notes
Load accounted for includes 0.53 kPa permanent timber floor, 0.4 kPa permanent metal roof, 1.16 kN/m permanent wall, permanent member self-weight, 1.5 kPa or 1.1 kN imposed floor and 0.25 kPa imposed roof.
Load combinations included are G + 0.5Q for ULS.
Minimum bearing pressure is 100 kPa for pad footings.
A roof load area of “0” must be used for footings not supporting roof loads.
The length of wall allowed for is equal to the square root of the floor area.
Table 4.2.20e Localised thickening under concentrated load — timber floor and metal roof — roof load area = maximum 9 m2
Localised thickening
Maximum floor load area (m2)
4
10
16
Square thickening size (mm)
500 x 500
700 x 700
800 x 800
Thickening depth (mm)
300
350
400
Table Notes
Load accounted for includes 0.53 kPa permanent timber floor, 0.4 kPa permanent metal roof, 1.16 kN/m permanent wall, permanent member self-weight, 1.5 kPa or 1.1 kN imposed floor and 0.25 kPa imposed roof.
Load combinations included are G + 0.5Q for ULS.
Minimum bearing pressure is 100 kPa for pad footings.
The length of wall allowed for is equal to the square root of the floor area.
Table 4.2.20f Localised thickening under concentrated load — timber floor and metal roof — roof load area = maximum 18 m2
Localised thickening
Maximum floor load area (m2)
4
10
16
Square thickening size (mm)
600 x 600
750 x 750
850 x 850
Thickening depth (mm)
300
400
450
Table Notes
Load accounted for includes 0.53 kPa permanent timber floor, 0.4 kPa permanent metal roof, 1.16 kN/m permanent wall, permanent member self-weight, 1.5 kPa or 1.1 kN imposed floor and 0.25 kPa imposed roof.
Load combinations included are G + 0.5Q for ULS.
Minimum bearing pressure is 100 kPa for pad footings.
The length of wall allowed for is equal to the square root of the floor area.
Figure 4.2.20 Localised thickening for concentrated loads
Tables
- Table 4.2.20a Localised thickening under concentrated load — tiled floor and tiled roof — roof load area = 0 m2
- Table 4.2.20b Localised thickening under concentrated load — tiled floor and tiled roof — roof load area = maximum 9 m2
- Table 4.2.20c Localised thickening under concentrated load — tiled floor and tiled roof — roof load area = maximum 18 m2
- Table 4.2.20d Localised thickening under concentrated load — timber floor and metal roof — roof load area = 0 m2
- Table 4.2.20e Localised thickening under concentrated load — timber floor and metal roof — roof load area = maximum 9 m2
- Table 4.2.20f Localised thickening under concentrated load — timber floor and metal roof — roof load area = maximum 18 m2
Changed since NCC 2022. See ABCB Housing Provisions 2022 4.2.20, or show what changed.
Where a footing or slab supports a concentrated load from … are G + 0.5Q for ULS. Minimum bearing pressure is 1000 100 kPa for pad footings. The length of wall allowed for … are G + 0.5Q for ULS. Minimum bearing pressure is 1000 100 kPa for pad footings. The length of wall allowed for … are G + 0.5Q for ULS. Minimum bearing pressure is 1000 100 kPa for pad footings. A roof load area of “0” … are G + 0.5Q for ULS. Minimum bearing pressure is 1000 100 kPa for pad footings. The length of wall allowed for … are G + 0.5Q for ULS. Minimum bearing pressure is 1000 100 kPa for pad footings. The length of wall allowed for … the floor area. Figure 4.2.20 Localised thickening for concentrated loads
Removed words are struck through; added words are highlighted. Comparison of the text only.