Table · ABCB Housing Provisions 2025

Table 4.2.20e Localised thickening under concentrated load — timber floor and metal roof — roof load area = maximum 9 m2

Part 4.2 Footings, slabs and associated elements

Open Table 4.2.20e on NCC Online ↗
Localised thickeningMaximum floor load area (m2)
41016
Square thickening size (mm)500 x 500700 x 700800 x 800
Thickening depth (mm)300350400

Table Notes

Load accounted for includes 0.53 kPa permanent timber floor, 0.4 kPa permanent metal roof, 1.16 kN/m permanent wall, permanent member self-weight, 1.5 kPa or 1.1 kN imposed floor and 0.25 kPa imposed roof.

Load combinations included are G + 0.5Q for ULS.

Minimum bearing pressure is 100 kPa for pad footings.

The length of wall allowed for is equal to the square root of the floor area.

Table for 4.2.20 Concentrated loads

Changed since NCC 2022 (minor wording). See ABCB Housing Provisions 2022 Table 4.2.20e, or show what changed.

Localised thickening | Maximum floor load area (m2) 4 | … are G + 0.5Q for ULS. Minimum bearing pressure is 1000 100 kPa for pad footings. The length of wall allowed for is equal to the square root of the floor area.

Removed words are struck through; added words are highlighted. Comparison of the text only.

Defined terms used