Table 4.2.20d Localised thickening under concentrated load — timber floor and metal roof — roof load area = 0 m2
Part 4.2 Footings, slabs and associated elements
| Localised thickening | Maximum floor load area (m2) | ||
|---|---|---|---|
| 4 | 10 | 16 | |
| Square thickening size (mm) | 400 x 400 | 600 x 600 | 750 x 750 |
| Thickening depth (mm) | 250 | 300 | 350 |
Table Notes
Load accounted for includes 0.53 kPa permanent timber floor, 0.4 kPa permanent metal roof, 1.16 kN/m permanent wall, permanent member self-weight, 1.5 kPa or 1.1 kN imposed floor and 0.25 kPa imposed roof.
Load combinations included are G + 0.5Q for ULS.
Minimum bearing pressure is 100 kPa for pad footings.
A roof load area of “0” must be used for footings not supporting roof loads.
The length of wall allowed for is equal to the square root of the floor area.
Table for 4.2.20 Concentrated loads
Changed since NCC 2022 (minor wording). See ABCB Housing Provisions 2022 Table 4.2.20d, or show what changed.