Table · ABCB Housing Provisions 2025
Table 5.6.5c Placement of wall ties
Part 5.6 Masonry components and accessories
| Location | Placement of wall ties |
|---|---|
| Unsupported panel sides and edges of openings | Within 300 mm of panel side or edge |
| Top of veneer panels and top of panels under openings | Within 300 mm or two courses (whichever is the lesser) of the top of veneer |
| Bottom of veneer panel in masonry rebate sealed with liquid applied damp-proof course | Within 300 mm or two courses (whichever is the lesser) from the bottom of the veneer |
| Bottom of veneer panel in masonry rebate with membrane damp-proof course | In each of the first two courses |
| Intersection of internal walls and external walls | 350 mm vertically or 3-4 courses |
| Where articulation joints occur | At both sides of the articulation joint within 300 mm from the joint |
| Engaged piers | Within 200 mm of the top of the pier |
Bottom of veneer panel supported on steel lintel
Table Notes
Ties to be embedded a minimum of 50 mm into each masonry leaf.
Masonry wall ties must be installed in such a manner as to prevent moisture travelling along the tie to the inner leaf of masonry or the frame.
Table for 5.6.5 Wall ties
Same wording in ABCB Housing Provisions 2022. See ABCB Housing Provisions 2022 Table 5.6.5c.