Table 6.3.6d Required column section — columns supporting timber floor and metal roof load — roof load area = 0 m2

Part 6.3 Structural steel members

Open Table 6.3.6d on NCC Online ↗
Column sectionEffective height (mm)Floor load area (m2)
41016
CHS 250240060.3 x 3.6 CHS76.1 x 5.9 CHS101.6 x 5 CHS
CHS 250270060.3 x 3.6 CHS76.1 x 5.9 CHS101.6 x 5 CHS
CHS 250300060.3 x 4.5 CHS76.1 x 5.9 CHS101.6 x 5 CHS
CHS 250330060.3 x 4.5 CHS76.1 x 5.9 CHS101.6 x 5 CHS
CHS 250360060.3 x 4.5 CHS88.9 x 5 CHS101.6 x 5 CHS
CHS 350240060.3 x 2.3 CHS88.9 x 2.6 CHS101.6 x 3.2 CHS
CHS 350270060.3 x 2.9 CHS88.9 x 2.6 CHS114.3 x 3.2 CHS
CHS 350300060.3 x 2.9 CHS88.9 x 3.2 CHS114.3 x 3.2 CHS
CHS 350330060.3 x 2.9 CHS88.9 x 3.2 CHS114.3 x 3.2 CHS
CHS 350360060.3 x 2.9 CHS88.9 x 3.2 CHS114.3 x 3.2 CHS
SHS 350240065 x 65 x 2 SHS89 x 89 x 3.5 SHS100 x 100 x 3 SHS
SHS 350270065 x 65 x 2 SHS89 x 89 x 3.5 SHS100 x 100 x 3 SHS
SHS 350300065 x 65 x 2 SHS89 x 89 x 3.5 SHS100 x 100 x 3 SHS
SHS 350330065 x 65 x 2 SHS89 x 89 x 3.5 SHS100 x 100 x 3 SHS
SHS 350360065 x 65 x 2 SHS89 x 89 x 3.5 SHS100 x 100 x 3 SHS
SHS 450240050 x 50 x 2 SHS75 x 75 x 2.5 SHS89 x 89 x 3.5 SHS
SHS 450270050 x 50 x 2 SHS75 x 75 x 2.5 SHS89 x 89 x 3.5 SHS
SHS 450300050 x 50 x 2 SHS75 x 75 x 2.5 SHS89 x 89 x 3.5 SHS
SHS 450330050 x 50 x 2.5 SHS89 x 89 x 3.5 SHS89 x 89 x 3.5 SHS
SHS 450360050 x 50 x 2.5 SHS89 x 89 x 3.5 SHS89 x 89 x 3.5 SHS

Table Notes

Load accounted for includes 0.53 kPa permanent floor, 1.16 kN/m permanent wall, 0.4 kPa permanent roof, permanent member self-weight, 1.5 kPa or 1.1 kN imposed floor and 0.25 kPa imposed roof.

Load combinations included are 1.35G and 1.2G + 1.5Q for ULS.

Columns are assumed to be simply-supported at both ends with an effective length factor of 1.

A maximum load eccentricity of 100 mm has been accounted for in the columns.

A roof load area of “0” must be used for columns not supporting roof loads.

The length of wall load allowed for is equal to the square root of the floor area.

Table for 6.3.6 Columns

Same wording in ABCB Housing Provisions 2022. See ABCB Housing Provisions 2022 Table 6.3.6d.