Performance Requirement · NCC 2025 Volume Three

B1P5 Water efficiency

Part B1 Cold water services · NCC 2019: BP1.2, TAS Exemption 1

Open B1P5 on NCC Online ↗
Varied in NSW. Check the variation for your state.

Where a cold water service is used, efficient use of drinking water must be achieved by—

incorporation of—

a tap or outlet for a shower, basin, kitchen sink or laundry trough, to a flow rate of not more than 9 l/m; and

a cistern or flushing device for a urinal, to a flush volume of not more than 2.5 litres for each—

single urinal stall; or

600 mm length of a continuous urinal wall; and

a dual flush cistern or flushing valve that is connected to a water closet pan to a flush volume of not more than—

6 and 3 litres; or

4.5 and 3 litres; or

water saving measures equivalent to or greater than those described in (a).

Applications

The flush volumes of B1P5 may be within a tolerance of—

±0.5 litres for the full flush of a 6/3 litre cistern; or

+0.5 litres for the reduced flush of a 6/3 litre cistern; or

±0.2 litres for a 4.5/3 litre cistern.

Exemptions

The requirements of B1P5 do not apply to a vacuum drainage system.

Changed since NCC 2022. See NCC 2022 Volume Three B1P5, or show what changed.

The points of discharge for Where a cold water service is used, efficient use of drinking water must be achieved by — have incorporation of — a working pressure of not less than 50 kPa; and tap or outlet for a static pressure within the building shower, basin, kitchen sink or laundry trough, to a flow rate of not more than 500 kPa; 9 l/m; and a cistern or have flushing device for a urinal, to a flush volume of not more than 2.5 litres for each — single urinal stall; or 600 mm length of a continuous urinal wall; and a dual flush cistern or flushing valve that is connected to a water pressures suitable closet pan to a flush volume of not more than — 6 and 3 litres; or 4.5 and 3 litres; or water saving measures equivalent to or greater than those described in (a). Applications The flush volumes of B1P5 may be within a tolerance of — ±0.5 litres for the correct functioning full flush of a 6/3 litre cistern; or +0.5 litres for the fixture reduced flush of a 6/3 litre cistern; or appliance where water pressures outside ±0.2 litres for a 4.5/3 litre cistern. Exemptions The requirements of (a)(i) and (a)(ii) are required. B1P5 do not apply to a vacuum drainage system.