NCC 2025 Volume Three
Part B1 Cold water services
19 clauses · Open on NCC Online ↗
- B1O1 ObjectiveThe Objective of this Part is to— safeguard people from illness, injury or loss (including loss of amenity) due to the failure of a cold water…
- B1F1 Cold water supplySanitary fixtures, sanitary appliances and supply outlets providing drinking water must have a safe and adequate piped cold water supply.
- B1F2 Cold water serviceThe cold water service must be conveyed through plumbing installations in a way that minimises any adverse impact on building occupants, the Network…
- B1F3 Fire sprinkler systemsResidential fire sprinkler equipment must be provided with adequate water supply and pressure for its intended purpose.
- B1P1 Cold water supplyA cold water service must be connected to a drinking water supply. Applications B1P1 applies to cold water supplied for human consumption, food…
- B1P2 VelocityWater velocity within cold water service pipework must not exceed 3 metres per second for no less than 99% of the time that water is required during…
- B1P3 AccessAccess must be provided to components of a cold water service that require maintenance or replacement including mechanical devices and controls.
- B1P4 IsolationA means of isolation must be provided to a cold water service and components that require testing, maintenance or replacement including mechanical…
- B1P5 Water efficiency NSWWhere a cold water service is used, efficient use of drinking water must be achieved by— incorporation of— a tap or outlet for a shower, basin,…
- B1P6 Pressure TASThe points of discharge for a cold water service must— have— a working pressure of not less than 50 kPa; and a static pressure within the building…
- B1P7 Uncontrolled dischargeAny failure or uncontrolled discharge from a cold water service must be avoided.
- Table B1V1 Fixture probability coefficientsFixture | Shower | 0.061 | 0.908 | -0.475 | 0.020 | -1.343 Tap | 0.009 | 1 | 0 | 0.004 | -0.880 Toilet | 0.002 | 1 | 0 | 0.002 | -0.880 Washing…
- B1V1 Determination of velocityCompliance with Performance Requirement B1P2 is verified for a cold-water service in a Class 2 or Class 3 building when the pipework diameter of…
- B1D1 Deemed-to-Satisfy ProvisionsPerformance Requirement B1P1 is satisfied if the cold water service is connected to— the Network Utility Operator’s drinking water supply; or an…
- B1D2 Water efficiency NSW QLDA tap or outlet used for a shower, basin, kitchen sink or laundry trough must be a minimum of 3 Star WELS rated and discharge not more than 9 litres…
- B1D3 General requirements NSW QLD TAS VICA cold water service must be in accordance with AS/NZS 3500.1. (2) Notwithstanding (1), plastic pipes and fittings must not be used above-ground in…
- B1D4 Bushfire prone areasA cold water service in a designated bushfire prone area must be in accordance with AS 3959.
- B1D5 Cold water fire sprinkler systemsA cold water service used for fire-fighting must be in accordance with— the requirements of E1 of Volume One, where applicable; and FPAA 101D when…
- B1D6 Top-up linesA cold water service used to top up a rainwater tank must be in accordance with AS/NZS 3500.1.